↓
Voltage Drop
Voltage drop limits, mV/A/m values, and calculation formula from BS 7671 Appendix 4.
Voltage Drop Limits
Maximum Permitted Voltage Drop
From the origin of the installation: • Lighting circuits: 3% (6.9V at 230V) • Other circuits: 5% (11.5V at 230V)
Note: These limits apply from the supply terminals to the most distant point of the circuit. Where the supply is from a public distribution system, an additional 0.5% is allowed.
BS 7671: Appendix 4
Flat Twin & Earth (PVC) mV/A/m
Flat Twin & Earth (PVC 70°C) mV/A/m
| Size (mm²) | 1Φ 2-core | 3Φ 3-core |
|---|---|---|
| 1.0 | 44 | 38 |
| 1.5 | 29 | 25 |
| 2.5 | 18 | 15 |
| 4.0 | 11 | 9.5 |
| 6.0 | 7.3 | 6.4 |
| 10.0 | 4.4 | 3.8 |
| 16.0 | 2.8 | 2.4 |
PVC 70°C copper conductors. For sizes ≤16mm², values are purely resistive and identical across installation methods.
BS 7671: Table 4D1B
Singles in Conduit (PVC) — Table 4D1B
Singles in Conduit (PVC 70°C) — Table 4D1B
| Size (mm²) | 1Φ 2-cable | 3Φ 3-cable |
|---|---|---|
| 1.0 | 44 | 38 |
| 1.5 | 29 | 25 |
| 2.5 | 18 | 15 |
| 4.0 | 11 | 9.5 |
| 6.0 | 7.3 | 6.4 |
| 10.0 | 4.4 | 3.8 |
| 16.0 | 2.8 | 2.4 |
Reference Methods A & B (enclosed in conduit/trunking). Values in mV/A/m.
BS 7671: Table 4D1B
Voltage Drop Formula
Voltage Drop
VD = (mV/A/m × Ib × L) / 1000
VD Voltage drop (Volts)
mV/A/m Table value (mV/A/m)
Ib Design current (Amperes)
L Cable length (metres)
Use 1Φ (2-core) values for single-phase circuits. Use 3Φ (3-core) values for three-phase circuits. The formula is the same — only the mV/A/m value changes.
BS 7671: Appendix 4
Open Calculator →