R

Conductor Resistance

R1+R2 values at 20°C and temperature correction factors from BS 7671 Appendix I.

R1+R2 at 20°C — Table I1

R1+R2 at 20°C — Table I1

Line (mm²)CPC (mm²)R1 (mΩ/m)R2 (mΩ/m)R1+R2 (mΩ/m)
1.01.018.1018.1036.20
1.51.012.1018.1030.20
2.51.57.4112.1019.51
4.01.54.6112.1016.71
6.02.53.087.4110.49
10.04.01.834.616.44
16.06.01.153.084.23
BS 7671: Table I1

Temperature Correction

R1+R2 at Operating Temperature

Rₜ = R₂₀ × [1 + 0.004 × (t - 20)]
Rₜ Resistance at temperature t (Ω)
R₂₀ Resistance at 20°C (Ω)
t Operating temperature (°C)

For PVC insulated cables at 70°C, the multiplier is 1.20. Simplified: R₇₀ = R₂₀ × 1.20