Correction Factors

Correction factors for ambient temperature, grouping, thermal insulation, and semi-enclosed fuses.

Ambient Temperature (Ca) — Table 4B1

Ambient Temperature Correction Factor (Ca)

Temp (°C)PVC (70°C)XLPE (90°C)
251.031.02
301.001.00
350.940.96
400.870.91
450.790.87
500.710.82
550.610.76
600.500.71
BS 7671: Table 4B1

Grouping Factor (Cg) — Table 4C1

Grouping Correction Factor (Cg)

No. of CircuitsBunched/EnclosedSingle Layer on WallSingle Layer Ceiling
11.001.000.95
20.800.850.81
30.700.790.72
40.650.750.68
50.600.730.66
60.570.720.64
70.540.720.63
80.520.710.62
90.500.700.61
120.450.700.61
160.410.700.61
200.380.700.61
BS 7671: Table 4C1

Thermal Insulation (Ci) — Reg 523.7

Thermal Insulation Correction Factor (Ci)

ConditionFactor (Ci)
Not enclosed in insulation1.00
One side touching insulation0.75
Totally surrounded 50mm0.89
Totally surrounded 100mm0.81
Totally surrounded 200mm0.68
Totally surrounded 400mm+0.55

For cables totally surrounded by thermal insulation for distances > 0.5m. Values from Table 52.2.

BS 7671: Reg 523.7

Semi-enclosed Fuse Factor (Cc)

When BS 3036 semi-enclosed (rewirable) fuses are used, apply a correction factor Cc = 0.725 to the tabulated cable current rating.

BS 7671: Reg 433.1.1