Cable Capacities
Current-carrying capacities (Iz) for copper cables from BS 7671 Appendix 4 Tables 4D1A, 4D5, 4E4A and 4D4A.
Singles in Conduit (70°C Thermoplastic) — Table 4D1A
Singles in Conduit / Trunking — Table 4D1A, Iz (A)
| Size (mm²) | Method A 1Φ (col 2) | Method A 3Φ (col 3) | Method B 1Φ (col 4) | Method B 3Φ (col 5) |
|---|---|---|---|---|
| 1.0 | 11 | 10.5 | 13.5 | 12 |
| 1.5 | 14.5 | 13.5 | 17.5 | 15.5 |
| 2.5 | 20 | 18 | 24 | 21 |
| 4.0 | 26 | 24 | 32 | 28 |
| 6.0 | 34 | 31 | 41 | 36 |
| 10.0 | 46 | 42 | 57 | 50 |
| 16.0 | 61 | 56 | 76 | 68 |
| 25.0 | 80 | 73 | 101 | 89 |
| 35.0 | 99 | 89 | 125 | 110 |
| 50.0 | 119 | 108 | 151 | 134 |
| 70.0 | 151 | 136 | 192 | 171 |
| 95.0 | 182 | 164 | 232 | 207 |
| 120.0 | 210 | 188 | 269 | 239 |
| 150.0 | 240 | 216 | 300 | 262 |
| 185.0 | 273 | 245 | 341 | 296 |
| 240.0 | 321 | 286 | 400 | 346 |
| 300.0 | 367 | 328 | 458 | 394 |
Method A: enclosed in conduit in a thermally insulating wall. Method B: enclosed in conduit on a wall or in trunking.
1Φ: 2 cables, single-phase a.c. or d.c. 3Φ: 3 or 4 cables, three-phase a.c. Ambient 30 °C, conductor 70 °C.
Flat Twin & Earth (70°C Thermoplastic) — Table 4D5
Flat Twin & Earth — Table 4D5, Iz (A)
| Size (mm²) | Method A (col 6) | Method B (col 7) | Method C clipped direct (col 8) |
|---|---|---|---|
| 1.0 | 11.5 | 13 | 16 |
| 1.5 | 14.5 | 16.5 | 20 |
| 2.5 | 20 | 23 | 27 |
| 4.0 | 26 | 30 | 37 |
| 6.0 | 32 | 38 | 47 |
| 10.0 | 44 | 52 | 64 |
| 16.0 | 57 | 69 | 85 |
Flat T&E is a single-phase cable: Table 4D5 has no three-phase column, and it is tabulated to 16 mm² only. Ambient 30 °C, conductor 70 °C.
Method A: in conduit in a thermally insulated wall. Method B: in conduit on a wall or in trunking. Installation Methods 100–103 (in insulated ceilings and stud walls) are separate columns of Table 4D5.
SWA Multicore (90°C Thermosetting) — Table 4E4A
Armoured Multicore, 90°C — Table 4E4A, Iz (A)
| Size (mm²) | Method C 1Φ (col 2) | Method C 3Φ (col 3) | Method E 1Φ (col 4) | Method D1 1Φ (col 6) |
|---|---|---|---|---|
| 1.5 | 27 | 23 | 29 | 25 |
| 2.5 | 36 | 31 | 39 | 33 |
| 4.0 | 49 | 42 | 52 | 43 |
| 6.0 | 62 | 53 | 66 | 53 |
| 10.0 | 85 | 73 | 90 | 71 |
| 16.0 | 110 | 94 | 115 | 91 |
| 25.0 | 146 | 124 | 152 | 116 |
| 35.0 | 180 | 154 | 188 | 139 |
| 50.0 | 219 | 187 | 228 | 164 |
| 70.0 | 279 | 238 | 291 | 203 |
| 95.0 | 338 | 289 | 354 | 239 |
| 120.0 | 392 | 335 | 410 | 271 |
| 150.0 | 451 | 386 | 472 | 306 |
| 185.0 | 515 | 441 | 539 | 343 |
| 240.0 | 607 | 520 | 636 | 395 |
| 300.0 | 698 | 599 | 732 | 446 |
90 °C ratings. Reg 512.1.5: use them only where the equipment manufacturer confirms the terminals are suitable for the conductor operating temperature; otherwise use Table 4D4A (70 °C), below.
1Φ: one two-core cable. 3Φ: one three- or four-core cable. Method E: free air or perforated tray. Method D1: in ducts in the ground, 20 °C ground, 2.5 K·m/W, 0.7 m deep; other methods 30 °C ambient.
SWA Multicore at 70°C Terminals — Table 4D4A
Armoured Multicore, 70°C — Table 4D4A, Iz (A)
| Size (mm²) | Method C 1Φ (col 2) | Method C 3Φ (col 3) | Method E 1Φ (col 4) | Method D1 1Φ (col 6) |
|---|---|---|---|---|
| 1.5 | 21 | 18 | 22 | 22 |
| 2.5 | 28 | 25 | 31 | 29 |
| 4.0 | 38 | 33 | 41 | 37 |
| 6.0 | 49 | 42 | 53 | 46 |
| 10.0 | 67 | 58 | 72 | 60 |
| 16.0 | 89 | 77 | 97 | 78 |
| 25.0 | 118 | 102 | 128 | 99 |
| 35.0 | 145 | 125 | 157 | 119 |
| 50.0 | 175 | 151 | 190 | 140 |
| 70.0 | 222 | 192 | 241 | 173 |
| 95.0 | 269 | 231 | 291 | 204 |
| 120.0 | 310 | 267 | 336 | 231 |
| 150.0 | 356 | 306 | 386 | 261 |
| 185.0 | 405 | 348 | 439 | 292 |
| 240.0 | 476 | 409 | 516 | 336 |
| 300.0 | 547 | 469 | 592 | 379 |
Use for 90 °C thermosetting SWA where the equipment terminals are rated for 70 °C conductors only (Reg 512.1.5 NOTE 3) — most MCBs, RCBOs and accessories unless the manufacturer states otherwise.
Method D1: in ducts in the ground, 20 °C ground, 2.5 K·m/W, 0.7 m deep; other methods 30 °C ambient.