Cable Capacities

Current-carrying capacities (Iz) for copper cables from BS 7671 Appendix 4 Tables 4D1A, 4D5, 4E4A and 4D4A.

Singles in Conduit (70°C Thermoplastic) — Table 4D1A

Singles in Conduit / Trunking — Table 4D1A, Iz (A)

Size (mm²)Method A 1Φ (col 2)Method A 3Φ (col 3)Method B 1Φ (col 4)Method B 3Φ (col 5)
1.01110.513.512
1.514.513.517.515.5
2.520182421
4.026243228
6.034314136
10.046425750
16.061567668
25.0807310189
35.09989125110
50.0119108151134
70.0151136192171
95.0182164232207
120.0210188269239
150.0240216300262
185.0273245341296
240.0321286400346
300.0367328458394

Method A: enclosed in conduit in a thermally insulating wall. Method B: enclosed in conduit on a wall or in trunking.

1Φ: 2 cables, single-phase a.c. or d.c. 3Φ: 3 or 4 cables, three-phase a.c. Ambient 30 °C, conductor 70 °C.

BS 7671: Table 4D1A Open Calculator →

Flat Twin & Earth (70°C Thermoplastic) — Table 4D5

Flat Twin & Earth — Table 4D5, Iz (A)

Size (mm²)Method A (col 6)Method B (col 7)Method C clipped direct (col 8)
1.011.51316
1.514.516.520
2.5202327
4.0263037
6.0323847
10.0445264
16.0576985

Flat T&E is a single-phase cable: Table 4D5 has no three-phase column, and it is tabulated to 16 mm² only. Ambient 30 °C, conductor 70 °C.

Method A: in conduit in a thermally insulated wall. Method B: in conduit on a wall or in trunking. Installation Methods 100–103 (in insulated ceilings and stud walls) are separate columns of Table 4D5.

BS 7671: Table 4D5 Open Calculator →

SWA Multicore (90°C Thermosetting) — Table 4E4A

Armoured Multicore, 90°C — Table 4E4A, Iz (A)

Size (mm²)Method C 1Φ (col 2)Method C 3Φ (col 3)Method E 1Φ (col 4)Method D1 1Φ (col 6)
1.527232925
2.536313933
4.049425243
6.062536653
10.085739071
16.01109411591
25.0146124152116
35.0180154188139
50.0219187228164
70.0279238291203
95.0338289354239
120.0392335410271
150.0451386472306
185.0515441539343
240.0607520636395
300.0698599732446

90 °C ratings. Reg 512.1.5: use them only where the equipment manufacturer confirms the terminals are suitable for the conductor operating temperature; otherwise use Table 4D4A (70 °C), below.

1Φ: one two-core cable. 3Φ: one three- or four-core cable. Method E: free air or perforated tray. Method D1: in ducts in the ground, 20 °C ground, 2.5 K·m/W, 0.7 m deep; other methods 30 °C ambient.

BS 7671: Table 4E4A

SWA Multicore at 70°C Terminals — Table 4D4A

Armoured Multicore, 70°C — Table 4D4A, Iz (A)

Size (mm²)Method C 1Φ (col 2)Method C 3Φ (col 3)Method E 1Φ (col 4)Method D1 1Φ (col 6)
1.521182222
2.528253129
4.038334137
6.049425346
10.067587260
16.089779778
25.011810212899
35.0145125157119
50.0175151190140
70.0222192241173
95.0269231291204
120.0310267336231
150.0356306386261
185.0405348439292
240.0476409516336
300.0547469592379

Use for 90 °C thermosetting SWA where the equipment terminals are rated for 70 °C conductors only (Reg 512.1.5 NOTE 3) — most MCBs, RCBOs and accessories unless the manufacturer states otherwise.

Method D1: in ducts in the ground, 20 °C ground, 2.5 K·m/W, 0.7 m deep; other methods 30 °C ambient.

BS 7671: Table 4D4A Open Calculator →