Zs Values
Maximum earth fault loop impedance values for MCBs and fuses from BS 7671 Tables 41.2–41.6.
MCB Type B (Table 41.2)
MCB Type B — Max Zs Values
| Rating (A) | Max Zs 0.4s (Ω) | Max Zs 5s (Ω) |
|---|---|---|
| 6 | 7.67 | 12.88 |
| 10 | 4.60 | 7.73 |
| 16 | 2.87 | 4.83 |
| 20 | 2.30 | 3.86 |
| 25 | 1.84 | 3.09 |
| 32 | 1.44 | 2.41 |
| 40 | 1.15 | 1.93 |
| 50 | 0.92 | 1.54 |
| 63 | 0.73 | 1.23 |
BS 7671: Table 41.2
Open Calculator →
MCB Type C (Table 41.3)
MCB Type C — Max Zs Values
| Rating (A) | Max Zs 0.4s (Ω) | Max Zs 5s (Ω) |
|---|---|---|
| 6 | 3.83 | 6.44 |
| 10 | 2.30 | 3.86 |
| 16 | 1.44 | 2.41 |
| 20 | 1.15 | 1.93 |
| 25 | 0.92 | 1.54 |
| 32 | 0.72 | 1.21 |
| 40 | 0.57 | 0.96 |
| 50 | 0.46 | 0.77 |
| 63 | 0.37 | 0.61 |
BS 7671: Table 41.3
MCB Type D (Table 41.4)
MCB Type D — Max Zs Values
| Rating (A) | Max Zs 0.4s (Ω) | Max Zs 5s (Ω) |
|---|---|---|
| 6 | 1.92 | 3.22 |
| 10 | 1.15 | 1.93 |
| 16 | 0.72 | 1.21 |
| 20 | 0.57 | 0.96 |
| 25 | 0.46 | 0.77 |
| 32 | 0.36 | 0.60 |
| 40 | 0.29 | 0.48 |
| 50 | 0.23 | 0.39 |
| 63 | 0.18 | 0.31 |
BS 7671: Table 41.4
BS 88 Fuses
BS 88 Fuses — Max Zs Values
| Rating (A) | Max Zs 0.4s (Ω) | Max Zs 5s (Ω) |
|---|---|---|
| 6 | 8.89 | 14.0 |
| 10 | 5.33 | 8.57 |
| 16 | 2.80 | 4.18 |
| 20 | 1.78 | 3.04 |
| 25 | 1.41 | 2.10 |
| 32 | 1.09 | 1.63 |
| 40 | 0.86 | 1.18 |
| 50 | 0.55 | 0.87 |
| 63 | 0.43 | 0.62 |
| 80 | 0.32 | 0.47 |
| 100 | 0.25 | 0.36 |
BS 7671: Table 41.6
BS 3036 Fuses
BS 3036 Fuses — Max Zs Values
| Rating (A) | Max Zs 0.4s (Ω) | Max Zs 5s (Ω) |
|---|---|---|
| 5 | 10.9 | 18.3 |
| 15 | 3.43 | 5.58 |
| 20 | 2.44 | 3.83 |
| 30 | 1.48 | 2.39 |
| 45 | 0.96 | 1.41 |
| 60 | 0.58 | 0.96 |
| 100 | 0.27 | 0.46 |
BS 7671: Table 41.5