Part 4ProtectionRCDSafety

What Is an RCD? How It Works, Types, and When BS 7671 Requires One

IET Wiring Regulations Team ·

The Residual Current Device — the RCD — is one of the most important protective devices in modern electrical installations. It provides additional protection against electric shock by detecting current leakage to earth and disconnecting the supply in milliseconds — far faster than an MCB or fuse could react.

 

Understanding how RCDs work, the different types available, and where BS 7671 requires them is essential for the IET exam. This guide covers all of it.

 

How an RCD Works

An RCD monitors the current flowing in the Line and Neutral conductors of a circuit. Under normal conditions, the current flowing out on the Line is exactly equal to the current returning on the Neutral — the two cancel each other out.

 

If a fault occurs — say, current leaks through a person touching a live part to earth — some current takes a different path and doesn’t return via the Neutral. The RCD detects this imbalance and trips.

 

How an RCD works — detecting current imbalance

 

The Core Transformer

Inside every RCD is a toroidal (ring-shaped) current transformer. Both the Line and Neutral conductors pass through this core.

 

ConditionWhat Happens in the CoreResult
Normal operationLine current magnetic field is exactly opposed by Neutral current — net magnetic flux is zeroNo voltage is induced in the sensing coil — the RCD stays on
Leakage to earthLess current returns via the Neutral — magnetic fields don’t cancel — net flux in the coreVoltage is induced in the sensing coil — trip mechanism disconnects the supply

 

Key point: A 30mA RCD trips well below the level that would cause a fatal electric shock (typically 50mA and above for sustained periods).

 

Types of RCD

Types of RCD protection

 

TypeRatingsProtectionAdvantage
RCCB (Residual Current Circuit Breaker)63A or 80A, 30 mA sensitivityEarth fault protection only — no overload or short circuit protection. Requires individual MCBs downstreamOften found in split-load consumer units protecting a group of circuits
RCBO (Residual Current Breaker with Overcurrent)6A to 40A, 30 mA, Type BEarth fault, overload, AND short circuit protection in a single deviceA fault on one circuit only trips that RCBO — all other circuits remain live. The preferred solution for full discrimination
RCD Socket Outlet30 mA sensitivityEarth fault protection for whatever is plugged into the socketSelf-contained — useful for outdoor sockets, garages, and retrofitting older installations without RCD protection at the consumer unit

 

Where BS 7671 Requires RCD Protection

Regulation 411.3.3 is the key regulation. A 30 mA RCD is required for:

 

Where BS 7671 requires RCD protection

 

Key Requirements

ScenarioRequirementRegulation
Socket outlets ≤ 32AMust have 30 mA RCD protectionReg. 411.3.3
TT systemsAll circuits require RCD protection for fault protection, since the high Ze means overcurrent devices can’t clear faults fast enoughReg. 411.5.2
Cables in wallsIf cables are installed at a depth less than 50 mm and are not otherwise protected, 30 mA RCD protection is requiredReg. 522.6.202
BathroomsAll circuits in locations containing a bath or shower require 30 mA RCD protectionReg. 701.411.3.3
Outdoor equipmentCircuits supplying outdoor lighting and equipment require 30 mA RCD protectionReg. 714.411.3.3

 

Exceptions

Not every socket needs RCD protection. Exceptions include:

ExceptionDetail
Labelled socket outletsFor specific items of equipment, labelled and maintained by a skilled or instructed person
Non-outdoor portable useSocket outlets not expected to supply portable equipment used outdoors
Industrial applicationsSpecific applications where risk assessment justifies an alternative approach

 

RCD Testing

RCDs must be tested both by the user (via the test button) and by an electrician (using a calibrated RCD tester).

 

Test Button

Every RCD has a test button that simulates a small leakage. BS 7671 recommends pressing this button every 6 months to check mechanical operation (the notice wording was updated from quarterly to 6-monthly in Amendment 2:2022, Reg. 514.12.2). The test button only checks the mechanism — it does not verify the trip time or trip current.

 

Remember: The test button only checks the mechanism — it does not verify the trip time or trip current. Instrument testing is required for full verification.

 

Instrument Testing (Regulation 612.13)

During initial verification and periodic inspection, an electrician tests the RCD with a calibrated instrument that injects a known test current:

TestCurrent AppliedMaximum Trip Time
1× rated residual current (IΔn)30 mA (for a 30 mA RCD)300 ms
5× rated residual current150 mA40 ms
½× rated residual current15 mAMust NOT trip
Ramp test (optional)Gradually increasingRecords actual trip current

 

Exam Tip: The half-rated test (½× IΔn) is important — it confirms the RCD doesn’t trip too easily, which would cause nuisance tripping. The RCD must NOT trip at half its rated residual current.

 

RCD vs MCB — What’s the Difference?

FeatureMCBRCD (RCCB)RCBO
Overload protection
Short circuit protection
Earth fault protection
Additional protection
DetectsOvercurrentCurrent imbalanceBoth
Trip speed (earth fault)Up to 5 secondsUnder 300 msUnder 300 ms

 

Warning: An RCD is not a substitute for an MCB — they protect against different things. An RCCB needs MCBs downstream. Only an RCBO provides all three types of protection in one device.

 

Common Exam Questions

QuestionAnswer
”What does an RCD detect?”An imbalance between Line and Neutral current
”What trip current for additional protection?“30 mA (Reg. 415.1.1)
“Maximum trip time at IΔn?“300 ms
”Maximum trip time at 5× IΔn?“40 ms
”Why is RCD essential on TT systems?”High Ze means MCBs can’t clear earth faults fast enough
”How often should the test button be pressed?”Every 6 months (Reg. 514.12.2, updated in A2:2022)
“Does an RCCB provide overload protection?”No — MCBs are needed downstream

 

Key Regulations

RegulationRequirement
Reg. 411.3.3Additional protection by RCDs (≤ 30 mA) for socket outlets ≤ 32A
Reg. 411.5.2RCD required for fault protection on TT systems
Reg. 415.1.1Additional protection: RCD with IΔn ≤ 30 mA
Reg. 522.6.202–203RCD protection for cables in walls
Reg. 531.2Requirements for RCDs
Reg. 612.13RCD testing during verification
Reg. 701.411.3.3RCD requirements for bathrooms

 

Practice and Further Study

RCD protection is covered under Part 4: Protection for Safety of BS 7671. Test your knowledge:

 

Study on the go with our mobile app: App Store | Google Play

Prepare for your exam with our mobile app

580+ practice questions with detailed explanations