Part 5Wiring

The On-Site Guide: How to Use the Standard Final Circuit Tables

IET Wiring Regulations Team ·
The On-Site Guide: How to Use the Standard Final Circuit Tables

The On-Site Guide (OSG) is one of the most useful books you can keep in your toolbox — that little brown A5 companion to BS 7671. It condenses the calculations behind standard final circuits into a handful of lookup tables, so you can select a cable size, a protective device, an installation method and a maximum circuit length in seconds.

 

But it catches people out. The tables are dense, the numbering is unfamiliar, and — confusingly — the section that trips everyone up is called Part 7, which has nothing to do with Part 7 of BS 7671. This guide walks through exactly how those tables fit together, using a worked example, and finishes with a set of memory aids for the installation reference methods that come up again and again.

 

If you understand this, you’ll answer a whole class of Part 5 exam questions far faster — and you’ll be quicker on site too.

Part 7 of the OSG Is Not Part 7 of BS 7671

This is the single biggest source of confusion, so let’s clear it up first.

 

Book”Part 7” Means
BS 7671 (the brown Wiring Regs)Special installations and locations — bathrooms, construction sites, EV charging
On-Site GuideStandard final circuit tables — cable sizes, protective devices, maximum lengths

 

Important: When someone says “Part 7 of the On-Site Guide”, they mean the standard final circuit section — not special locations. Keep the two books straight in your head or you’ll waste time flicking to the wrong tables.

 

Part 7 of the OSG deals only with final circuits using copper conductors, and for ring circuits it assumes the circuit starts and finishes at the consumer unit or distribution board.

 

The Assumptions Behind the Tables

Every OSG table is built on a set of assumptions (set out on the first page of the section). If your installation doesn’t match them, the table result doesn’t apply and you need to calculate from first principles instead.

 

AssumptionValue
ConductorsCopper only
Earthing systemsTN-C-S, TN-S, or TT (with 30mA RCD/RCBO)
Ambient air temperatureNot exceeding 30°C (cooler is better)
Disconnection time≤ 0.4s for circuits up to 63A, with Cmin of 0.95
Voltage drop3% for lighting, 5% for all other circuits
Installation methodsAs listed in the OSG method tables

 

Key point: The 3% and 5% voltage drop limits come straight from Regulation 525 of BS 7671. On a 230V single-phase circuit, 5% is 11.5V — that’s the budget the length tables are working to.

 

Step 1: Find the Assumed Maximum Load

Start with Table 7.1(1). You need three things: what the protective device is, its rating, and the type of circuit.

 

Take our worked example — a 32A BS EN 60898 Type B circuit breaker protecting a ring final circuit. The table gives:

 

ParameterValue
Protective device32A BS EN 60898 Type B MCB
Assumed maximum load26A
Maximum Ze0.35Ω
Maximum measured Zs1.1Ω

 

The assumed maximum load of 26A (not 32A) reflects diversity — in a domestic setting, not every socket is loaded and not every appliance runs at once. The circuit isn’t expected to carry a continuous 32A.

 

Exam tip: A common trick question asks for the “assumed maximum load” of a standard ring final circuit. The answer is 26A, not the 32A rating of the protective device. Diversity is doing the work here.

 

Step 2: Check the Maximum Zs

The maximum measured Zs for the protective device comes from the OSG’s earth fault loop impedance table (Table B6). Find the device type down the left, the rating along the top, and read off where they cross.

 

For a Type B 32A device, the maximum measured Zs is 1.1Ω.

 

Remember: This 1.1Ω is a measured value — it has already been adjusted for a Cmin of 0.95 and the 80% temperature correction. There is nothing further for you to do to it. Don’t apply the 80% rule a second time.

 

That last point catches people out constantly. If you’re comparing an on-site loop impedance reading against a value from the tabulated measured Zs column, the correction is baked in. The 80% adjustment only applies when you’re working against the maximum Zs values in Table 41.3 of BS 7671, which are quoted at operating temperature. For a full walkthrough of that distinction, see our guide on Testing Zs: Earth Fault Loop Impedance Explained.

 

Step 3: Read the Standard Circuit Table

Now to the main event — the large standard circuit table, Table 7.1(2). It’s full of choices, so work through it in order.

 

Find the ring final circuits section, then locate your protective device. For a 32A Type B MCB, the table specifies:

 

ColumnResult
Cable2.5mm² twin and earth with 1.5mm² CPC
Permitted installation methods100, 102, A and C
Earthing / RCDTN-C-S, Ze ≤ 0.35Ω, 30mA RCD
Maximum circuit length106 m

 

That 106m is measured all the way around the ring — from the consumer unit, around the circuit, and back to the board. Choose reference method 100 (clipped direct to joists, thermal insulation not more than 100mm), pick the earthing system, confirm the 30mA RCD, and the length falls out of the table.

 

Key point: Every input changes the output. Swap the earthing system, the installation method or the protective device and the maximum length shifts. The tables aren’t a single answer — they’re a decision tree.

 

Ring vs Radial — Always Check

Here’s where people get burned. Assume that because a 32A ring reaches 106m, a 32A radial will be similar. It won’t.

 

Radial circuits with a terminal load (all the load at the far end — think of a shower or a cooker) are on a separate page of the same table. Look at what happens to a 32A radial:

 

Circuit TypeCableApprox. Max Length
Ring final (32A)2.5mm²106 m
Radial, terminal load (32A)4mm²Much shorter
Radial, terminal load (32A)6mm²Shorter still than the ring
Radial, terminal load (32A)10mm²~105 m

 

The only way to get a 32A radial close to the ring’s 106m is to jump up to 10mm² twin and earth. That’s a big difference in cable cost and installation effort.

 

Warning: Never split a ring into two radials without checking the radial tables first. Sometimes it simply won’t work safely with the existing cable. Ring and radial circuits must be treated separately — the maths behind them is different.

 

For more on why the two circuit types behave so differently, read Ring vs Radial Circuit Testing: Why the Methods Differ.

 

Installation Reference Methods Explained

The installation method decides how well the cable can shed heat — and therefore how much current it can carry. The OSG lists the methods and their current ratings (this data comes straight from Appendix 4 of BS 7671).

 

Look at a single 2.5mm² twin and earth cable across two methods:

 

Reference MethodDescriptionCurrent Rating
CClipped direct27 A
103Completely surrounded by thermal insulation13.5 A

 

Same cable — but surrounding it in insulation halves its capacity. This is exactly why installation method matters as much as cable size. For a deeper look at reading these tables, see Installation Reference Methods and Cable Sizing.

 

Memory Aids for Every Method

The reference method letters and numbers are hard to keep straight under exam pressure. Here’s a set of visual prompts that stick:

 

MethodMemory AidWhat It Is
AA for architraveCable in a gap behind an architrave, or conduit in a thermally insulated wall
BB for boxCable in conduit or trunking (a round or square “box”) clipped to a surface
CC for clipped directClipped direct, chased just below plaster, or on non-perforated cable tray
DD for dug inArmoured cable or conduit buried in the ground
E / FEdge, end or flatCables on a perforated cable tray (or in concrete trenches)

 

The 100-series methods are specific to flat twin and earth cable (the Regs call it “70°C thermoplastic insulated and sheathed flat cable”) — the ones you meet most in domestic work:

 

MethodMemory AidMeaning
100Insulation up to 100 mmCable in or above thermal insulation ≤ 100mm thick, touching joists/plasterboard
101101 is more than 100Insulation over 100mm thick
102Two plasterboard surfacesCable between two plasterboard faces — a stud wall
103At least three sides coveredSurrounded by insulation on three or more sides — worst case for heat

 

Exam tip: Method 103 gives the lowest current rating because the cable can’t shed heat. Whenever a question describes a cable “surrounded by insulation” or “in a thermally insulated wall for its whole length”, reach for the 103 column.

 

Common Mistakes with the OSG

The pitfalls that cost marks — and cause problems on site:

 

MistakeWhy It’s a Problem
Confusing OSG Part 7 with BS 7671 Part 7You end up in special locations instead of the standard circuit tables
Applying the 80% rule to a tabulated measured ZsThe correction is already built in — you’d double-count it
Assuming a radial matches the ring lengthRadials with a terminal load are far shorter for the same device
Ignoring the installation methodInsulation can halve a cable’s rating — 27A down to 13.5A
Using the tables outside their assumptionsAbove 30°C ambient, or non-standard earthing, the results don’t apply
Forgetting diversityThe assumed maximum load (26A) is not the device rating (32A)

 

Bottom line: The On-Site Guide is a shortcut, not a substitute for understanding. It works brilliantly when your installation matches the standard assumptions — and misleads you badly when it doesn’t. Always confirm the conditions before trusting the number.

 

Practice and Further Study

Standard final circuits, cable selection and installation methods are core Part 5 territory — and they appear on the 18th Edition exam every sitting. Test yourself across the topics:

 

Our app includes 690+ practice questions covering all 8 parts with detailed explanations referencing specific regulation numbers, plus full mock tests with the same weighted question distribution as the real exam — so you can practise reading tables under time pressure exactly as you’ll need to on the day.

 

Study on the go with our mobile app: App Store | Google Play

Prepare for your exam with our mobile app

690+ practice questions with detailed explanations