EV Charger Cable Calculation: A Complete Worked Example
Electric vehicle charger installations are now one of the most common jobs for domestic electricians — and they’re a growing topic in the IET exam. Section 722 of BS 7671 covers the specific requirements for EV charging installations, and it introduces several rules that differ from standard circuit design.
This guide walks through a complete cable sizing calculation for a typical domestic 7.4 kW charger, covering every step from design current to earth fault loop impedance verification.
EV Charger Types
Before calculating anything, you need to know what you’re installing. Most domestic installations use a Mode 3, single-phase, 7.4 kW charge point — often called a “wallbox.”
Key Points for Cable Sizing
- 7.4 kW single-phase = 32A at 230V — this is the standard domestic installation
- 22 kW three-phase = 32A per phase at 400V — commercial premises
- The charger draws 32A continuously for several hours — this is critical for cable sizing
The Continuous Load Problem
Here’s the single most important thing to understand about EV charging: Regulation 722.311 requires EV charging to be treated as a continuous load. This means:
- No diversity is applied — the cable must be rated for the full 32A, not a reduced figure
- The circuit is assumed to run at full load for 3 hours or more
- Standard domestic diversity factors (from BS 7671 Table 4A) do not apply to EV circuits
This is why a 32A EV circuit often needs a larger cable than a 32A cooker circuit — the cooker gets diversity applied, the EV charger does not.
Protection Requirements
Section 722 has specific protection requirements that differ from standard circuits.
RCD Protection (Regulation 722.531.3.101)
Every EV charging point must have its own dedicated circuit protected by:
- A 30 mA RCD — minimum Type A (to detect pulsating DC fault currents)
- If the charger can produce smooth DC leakage greater than 6 mA, a Type B RCD is required
- Many modern chargers have built-in DC leakage detection, which allows the use of a Type A RCD — check the manufacturer’s documentation
Overcurrent Protection
- A 32A MCB or RCBO (Type B curve is standard) on a dedicated circuit
- No other loads or socket outlets on the EV circuit
- An RCBO is the neatest solution as it provides both overcurrent and RCD protection in one device
PME Earthing (Regulation 722.411.4.1)
EV charging installations on PME (TN-C-S) supplies have additional earthing considerations. The 18th Edition Amendment 2 now permits PME earthing for EV charging, but you should check with the DNO for any local requirements — particularly for outdoor charge points.
Step-by-Step Cable Calculation
Let’s work through a real example.
The Scenario
- Charger: 7.4 kW single-phase wallbox (32A)
- Cable run: 20 metres from the consumer unit to the garage
- Installation method: Clipped direct (Method C), with thermal insulation contact on one side for 2 metres through an insulated wall
- Ambient temperature: 30°C (standard)
- Earthing system: TN-C-S, Ze = 0.35 Ω
- Protective device: 32A Type B RCBO
Step 1: Design Current (Ib)
The design current is the maximum current the circuit will carry in normal service.
Ib = P ÷ V = 7400 ÷ 230 = 32.17A
We round this to 32A since the charger is rated at 32A. The fundamental rule is: Ib ≤ In ≤ It.
Step 2: Protective Device Rating (In)
We need In ≥ Ib. A 32A Type B RCBO gives us In = 32A. This satisfies Ib ≤ In.
Step 3: Correction Factors
Now we calculate the overall correction factor to determine the minimum tabulated current rating (It) the cable must have.
| Factor | Value | Reason |
|---|---|---|
| Ca (ambient temperature) | 1.0 | 30°C ambient is the reference temperature for PVC cables |
| Cg (grouping) | 1.0 | Single circuit — no grouping derating needed |
| Ci (thermal insulation) | 0.75 | Cable touches thermal insulation on one side (Table 52.2) |
| Cf (semi-enclosed fuse) | 1.0 | Using an MCB/RCBO, not a BS 3036 fuse |
Overall correction factor = Ca × Cg × Ci = 1.0 × 1.0 × 0.75 = 0.75
Step 4: Minimum Tabulated Current (It)
It ≥ In ÷ CF = 32 ÷ 0.75 = 42.67A
Now look up the current-carrying capacity tables in Appendix 4 of BS 7671. For T&E cable clipped direct (Reference Method C, Table 4D5):
| Cable Size | It (Clipped Direct) |
|---|---|
| 4.0 mm² | 37A |
| 6.0 mm² | 47A |
| 10.0 mm² | 64A |
4.0 mm² only gives us 37A — that’s less than 42.67A, so it fails. 6.0 mm² gives 47A, which exceeds 42.67A. Select 6.0 mm² T&E.
Step 5: Voltage Drop Check
Regulation 525 limits the voltage drop to 5% of the nominal voltage for power circuits, which is:
Max VD = 230 × 0.05 = 11.5V
From Table 4D5, the mV/A/m value for 6.0 mm² T&E is 7.3 mV/A/m.
VD = (mV/A/m × Ib × L) ÷ 1000 = (7.3 × 32 × 20) ÷ 1000 = 4.67V
4.67V is well within the 11.5V limit — PASS.
Step 6: Earth Fault Loop Impedance (Zs)
Finally, verify that the earth fault loop impedance allows the protective device to disconnect within the required time.
Zs = Ze + (R1 + R2)
From the resistance tables (at 20°C):
- R1 for 6.0 mm² = 3.08 mΩ/m
- R2 for 2.5 mm² CPC = 7.41 mΩ/m
- R1 + R2 per metre = 10.49 mΩ/m
For 20 metres: (R1 + R2) = 10.49 × 20 ÷ 1000 = 0.21 Ω
Zs = 0.35 + 0.21 = 0.56 Ω
The maximum Zs for a 32A Type B MCB (Table 41.3, 0.4s disconnection) is 1.37 Ω. Our calculated Zs of 0.56 Ω is well within the limit — PASS.
When to Use SWA Cable
For outdoor or underground cable runs, T&E is not suitable. You should use:
- SWA (Steel Wire Armoured) cable — for buried or exposed outdoor runs
- Minimum depth: 500 mm below ground (with cable tiles or warning tape)
- SWA provides its own mechanical protection and can serve as the CPC (the steel wire armour)
- Common choice: 6.0 mm² 3-core SWA (or 2-core + armour as earth)
For runs that are entirely inside the building (e.g., consumer unit to an internal garage), clipped T&E is acceptable.
Common Exam Scenarios
| Scenario | Cable Size | Notes |
|---|---|---|
| 7.4 kW, 15 m, clipped direct, no derating | 6.0 mm² T&E | 4.0 mm² is too small (37A < 42.67A with Ci) |
| 7.4 kW, 30 m, clipped direct, no insulation | 6.0 mm² T&E | Check voltage drop: 7.3 × 32 × 30 = 7.0V (OK) |
| 7.4 kW, 40 m, clipped direct | 10.0 mm² T&E | VD with 6.0 mm²: 9.3V — tight. Consider 10.0 mm² |
| 7.4 kW, outdoor underground | 6.0 mm² SWA | Must use SWA for external/underground runs |
| 22 kW three-phase, commercial | 6.0 mm² 5-core SWA | 32A per phase, check per-phase VD |
Quick Reference Summary
| Parameter | Value |
|---|---|
| Standard domestic EV charger | 7.4 kW, 32A, single-phase |
| Protective device | 32A Type B RCBO (30 mA, Type A minimum) |
| Diversity factor | 1.0 (no diversity — continuous load) |
| Typical cable (internal) | 6.0 mm² T&E (6242Y) |
| Typical cable (external) | 6.0 mm² SWA |
| Maximum voltage drop | 5% of 230V = 11.5V |
| Key BS 7671 section | Section 722 |
Key Regulations
- Section 722 — Electric vehicle charging installations (entire section)
- Reg. 722.311 — Continuous load, diversity not applicable
- Reg. 722.411.4.1 — Earthing arrangements for PME supplies
- Reg. 722.531.3.101 — RCD protection requirements (Type A minimum)
- Reg. 722.433 — Overcurrent protection
- Table 4D5 — Current-carrying capacity for T&E cables (Reference Method C)
- Reg. 525 — Voltage drop limits
Practice and Further Study
EV charger cable calculation combines Part 4: Protection for Safety with Part 5: Selection and Erection and Section 722 of BS 7671. Test your knowledge:
Study on the go with our mobile app: App Store | Google Play