Part 4EarthingBondingProtection

Earthing and Bonding Explained: TN-C-S, TN-S, TT Systems & BS 7671 Requirements

IET Wiring Regulations Team ·

Earthing and bonding are the foundation of electrical safety. Every protective device in an installation — MCBs, RCDs, fuses — relies on a properly designed earth fault path to operate correctly. If the earthing or bonding is wrong, protection against electric shock fails.

 

This is also one of the most heavily tested topics in the IET exam. This guide covers the three earthing systems, main protective bonding, circuit protective conductors, conductor sizes, and the key BS 7671 regulations you need to know.

 

 

Why Do We Need Earthing?

The purpose of earthing is simple: if a fault occurs — say the live conductor touches the metal casing of an appliance — the fault current needs a low-resistance path back to the source so that the protective device (MCB, fuse, or RCD) can detect it and disconnect the supply quickly.

 

Key Principle: Without a low-resistance earth fault path, the metal casing of a faulty appliance sits at a dangerous voltage. Anyone touching it becomes the path to earth — through their body.

 

Regulation 411.3.1.1 of BS 7671 requires that, under earth fault conditions, the protective device must disconnect the circuit within:

Circuit TypeMaximum Disconnection Time
Socket outlets and portable equipment (up to 32A)0.4 seconds
Fixed equipment and distribution circuits5 seconds

 

Earth fault current path

 

The Three Earthing Systems

BS 7671 recognises three earthing systems, identified by a letter code:

LetterMeaningDescription
TTerre (earth)Connection to earth
NNeutralConnection to the supply neutral
CCombinedNeutral and earth are the same conductor
SSeparateNeutral and earth are separate conductors

 

The first letter describes the supply side (how the source is earthed). The second letter describes the installation side (how the installation is earthed).

 

The three earthing systems: TN-C-S, TN-S, and TT

 

SystemEarth SourceTypical ZeKey Characteristics
TN-C-S (PME)PEN conductor (combined neutral/earth from supply)0.35 ΩMost common UK system. Neutral and earth combined in supply cable, separated at consumer unit. Risk of open PEN fault.
TN-SMetal sheath of supply cable0.8 ΩNeutral and earth are separate throughout. Common in older underground networks. More reliable — no PEN conductor to fail.
TTLocal earth electrode (earth rod)20 Ω or moreNo earth provided by supply company. Common in rural areas with overhead lines. RCD protection is essential.

 

Warning: On TN-C-S (PME) systems, if the PEN conductor breaks (open PEN fault), all exposed metalwork connected to the earthing system can rise to a dangerous voltage. Because of this risk, there are restrictions on using PME earthing for certain situations — for example, it’s generally not permitted as the sole earth for swimming pools or caravan sites.

 

Main Protective Bonding

Main protective bonding connects extraneous conductive parts — metallic services entering the building that could introduce an earth potential — to the Main Earthing Terminal (MET).

 

The purpose is to ensure that all metalwork in the building is at the same potential. If a fault occurs, bonding prevents a dangerous voltage difference between, say, a gas pipe and an earthed appliance.

 

Main protective bonding and circuit protective conductors

 

What Must Be Bonded?

Under Regulation 411.3.1.2, the following extraneous conductive parts must be connected to the MET via main protective bonding conductors:

Extraneous Conductive PartNotes
Water service pipesMain incoming service
Gas service pipesConsumer’s side of meter
Oil supply pipesWhere metallic
Structural steelworkIf it forms an extraneous conductive part
Central heating systemsPipework and radiators
Lightning protection systemsWhere installed
Other metallic servicesAny metallic service entering the building

 

Where to Connect

Main bonding conductors must be connected within 600mm of the point of entry of the service into the building — and before any branch in the pipework. For gas, the connection must be on the consumer’s side of the meter, as close as practicable to the meter.

 

Exam Tip: The 600mm rule and the requirement to connect on the consumer’s side of the gas meter are frequently tested. Remember: within 600mm of entry, before any branch, and on the consumer’s side of the gas meter.

 

Conductor Sizes

One of the most commonly tested topics in the exam is knowing the minimum conductor sizes for different types of earthing and bonding conductors.

 

Minimum conductor sizes for earthing and bonding

 

Quick Reference: Minimum Conductor Sizes

ConductorMinimum Size (Cu)BS 7671 Reference
Main protective bonding10 mm²Reg. 544.1.1
Supplementary bonding4 mm²Reg. 544.2.3
Earthing conductor (bare, in contact with soil)16 mm²Table 54.8
Earthing conductor (mechanically protected)2.5 mm²Table 54.8
CPC (within cable)Per Table 54.7Reg. 543.1.1

 

Note: For supplies with a line conductor up to 35 mm², the main bonding conductor is 10 mm² Cu. For larger supplies, it must be proportionally larger (see Table 54.8).

 

The Main Earthing Terminal (MET)

The MET is the central connection point for the installation’s earthing system. Everything connects here:

  • The earthing conductor (from the means of earthing — supply earth or earth rod)
  • All main protective bonding conductors
  • The circuit protective conductors (CPCs) via the distribution board

 

Regulation 542.4.1 requires that the MET must be accessible for testing and inspection, and must allow individual conductors to be disconnected for measurement. In practice, this is often an earth bar inside or adjacent to the consumer unit.

 

Circuit Protective Conductors (CPCs)

The CPC is the earth conductor within each circuit cable (the bare copper wire in T&E cable, for example). Its job is to carry fault current from the point of the fault back to the MET and then to the source.

 

The size of the CPC depends on the size of the line conductor and is selected using Table 54.7 of BS 7671:

Line conductor (mm²)Minimum CPC (mm²)
Up to 16Same as line conductor
16 to 3516
Over 35Half of line conductor

 

In practice, the CPC size in standard T&E cable is often smaller than the line conductor (e.g., 2.5 mm² T&E has a 1.5 mm² CPC). This is important for calculating R1+R2 values during testing.

 

Common Exam Questions

Question TypeWhat to Remember
”What is the minimum size of main bonding?“10 mm² Cu (for supplies up to 35 mm²)
“On a TT system, what provides fault protection?”RCD protection (overcurrent devices can’t clear faults quickly enough)
“What does the first letter in TN-S mean?”T = the source (transformer) is directly connected to earth
”Where must main bonding be connected on gas?”Consumer’s side of the meter, within 600mm of entry
”What is the typical Ze for a TN-C-S system?“0.35 Ω
”Why is an open PEN fault dangerous?”All bonded metalwork can rise to supply voltage
”What disconnection time for a 32A socket circuit?“0.4 seconds

 

Key Regulations

For quick reference, here are the main BS 7671 regulations for earthing and bonding:

RegulationRequirement
Reg. 411.3.1.1Maximum disconnection times for fault protection
Reg. 411.3.1.2Main protective bonding requirements
Reg. 411.4.2TT system fault protection (RCD required)
Reg. 542.1Earthing arrangements general requirements
Reg. 542.4.1Main earthing terminal requirements
Reg. 543.1.1CPC sizing (Table 54.7)
Reg. 544.1.1Main bonding conductor sizing
Table 54.7Minimum CPC sizes related to line conductor
Table 54.8Minimum earthing conductor sizes

 

Practice and Further Study

Earthing and bonding falls under Part 4: Protection for Safety of BS 7671. Test your knowledge with our practice quizzes:

 

Study on the go with our mobile app: App Store | Google Play

Prepare for your exam with our mobile app

580+ practice questions with detailed explanations