Part 5WiringSafetyNeutral

The Dangers of a Shared (Borrowed) Neutral: Why Every Circuit Needs Its Own

IET Wiring Regulations Team ·

A shared neutral — sometimes called a “borrowed” neutral — is one of the most dangerous wiring faults found in older installations. It occurs when two or more circuits share a single neutral conductor instead of each having their own. While it might appear to “work” in normal operation, it creates serious safety hazards that can be lethal.

 

This is a topic that comes up regularly in the IET exam, particularly in questions about safe isolation, RCD operation, and circuit identification.

 

What Is a Shared Neutral?

In a correctly wired installation, every circuit has its own dedicated Line, Neutral, and Earth conductors running from the distribution board to the circuit. The neutral returns current from the load back to the neutral bar at the DB.

 

A shared neutral occurs when an installer has connected two (or more) circuits’ loads to the same neutral conductor — typically to save cable. Both circuits’ return currents flow through this single conductor.

 

The shared neutral problem

 

Why Is It Dangerous?

1. Neutral Overload

Each circuit’s MCB protects the Line conductor only. The neutral has no overcurrent protection. If two circuits each draw their rated current (say, 6A and 10A), the shared neutral carries the combined current of 16A — but it may only be rated for one circuit’s current.

 

This can cause the neutral conductor to overheat, damaging insulation and creating a fire risk.

 

2. Safe Isolation Fails

This is the most immediately dangerous consequence. If an electrician isolates Circuit 1 by switching off its MCB, they expect the circuit to be completely dead. But the shared neutral is still energised by Circuit 2.

 

Anyone working on what they believe is a dead circuit could receive a fatal electric shock from the neutral conductor — which is supposed to be at 0 V but is now carrying current from the other circuit.

 

3. Broken Neutral = Dangerous Voltages

If the shared neutral conductor breaks (at a connection, a terminal, or due to physical damage), the two loads end up effectively in series across the 230 V supply. The voltage splits between them in proportion to their resistance — and neither load gets the correct voltage.

 

What happens when a shared neutral breaks

 

The neutral conductor itself can rise to a significant voltage — potentially up to 230 V depending on the load balance. This creates a shock hazard on what should be a “safe” conductor.

 

4. RCDs Cannot Work Properly

An RCD detects the difference between current flowing on Line and returning on Neutral. If two circuits share a neutral, the RCD for Circuit 1 sees current going out on L1 but the return current splits between the proper N1 path and the shared path to Circuit 2.

 

This causes:

  • Nuisance tripping — the RCD sees an apparent leakage that doesn’t exist
  • Failure to trip on a real fault — the current paths are confused and the RCD may not detect a genuine earth leakage

 

5. Incorrect Test Results

During testing, a shared neutral produces misleading results:

  • Insulation resistance between L and N may read low due to the parallel path through the other circuit’s loads
  • Polarity testing may appear correct even though the wiring is wrong
  • Ring final circuit tests will give unexpected values

 

How to Identify a Shared Neutral

During inspection and testing, the following symptoms suggest a shared neutral:

SymptomWhat it indicates
RCD trips when a different circuit is loadedCurrent returning via the wrong neutral
Circuit remains live after MCB is switched offNeutral energised by another circuit
Insulation resistance between L–N is unexpectedly lowParallel path through connected loads on another circuit
Neutral conductor warm with only light loadCarrying return current from multiple circuits
Flickering lights when sockets are loadedShared neutral causing voltage fluctuations

 

What BS 7671 Says

Regulation 521.7.2 requires that every circuit must have its own neutral conductor where the neutral is not common to several circuits (i.e., multi-core cables). In practice, this means each circuit in a domestic installation must have a dedicated L, N, and E back to the distribution board.

 

Regulation 132.15 requires that installations allow for safe working — a shared neutral directly prevents safe isolation, violating this fundamental requirement.

 

Regulation 531.2.4 requires that the neutral of each circuit protected by an RCD passes through the RCD — shared neutrals violate this requirement.

 

What to Do If You Find One

If you discover a shared neutral during an inspection:

  1. Record it as a code C1 (danger present) or C2 (potentially dangerous) on the Electrical Installation Condition Report (EICR)
  2. Recommend remedial work — each circuit must have its own dedicated neutral
  3. Do not attempt to work on either circuit until the neutral has been properly separated
  4. If immediate work is needed, isolate both circuits at the DB and verify dead on both

 

Common Exam Questions

QuestionAnswer
”Why is a shared neutral dangerous for safe isolation?”Turning off one MCB doesn’t de-energise the neutral — still live from the other circuit
”What regulation prohibits shared neutrals?”Reg. 521.7.2
”How does a shared neutral affect an RCD?”Causes nuisance tripping or failure to trip on genuine faults
”What happens if a shared neutral breaks?”Loads go in series; neutral rises to dangerous voltage
”What EICR code for a shared neutral?”C1 or C2 depending on risk assessment

 

Key Regulations

  • Reg. 521.7.2 — Each circuit to have its own neutral
  • Reg. 132.15 — Installations must allow safe working
  • Reg. 531.2.4 — Neutral of each circuit through its RCD
  • Reg. 461.2 — Isolation must disconnect all live conductors
  • Reg. 514.9.1 — Identification of circuits

 

Practice and Further Study

Shared neutrals relate to Part 5: Selection and Erection of Equipment and testing under Part 6. Test your knowledge:

 

Study on the go with our mobile app: App Store | Google Play

Prepare for your exam with our mobile app

580+ practice questions with detailed explanations