Circuit Design and Overload Protection: Revision Notes for the 18th Edition
Circuit design is where the regulations stop being theoretical and start producing numbers. Cable size, device rating, voltage drop, disconnection time — get the design right and the circuit protects itself. Get it wrong and the cable cooks under load, or the protective device fails to clear a fault.
In the 18th Edition exam, circuit design and overload protection sit at the intersection of Part 4 (the rules) and Part 5 (the implementation), with Appendix 4 providing the data. Between them, these topics account for a substantial share of the paper — and they’re where calculation-based questions cluster.
These revision notes pull together the rules, the formulae, and the worked logic you need under exam conditions.
In This Guide
The Goal of Circuit Design
Every final circuit you design has to satisfy four things simultaneously:
| Requirement | Driven by | Reference |
|---|---|---|
| Safe under normal load | Cable current-carrying capacity (Iz) | Reg. 523 |
| Protected against overload | Coordination of Ib, In, Iz | Reg. 433 |
| Protected against fault current | Breaking capacity, energy let-through | Reg. 434 |
| Compliant disconnection time | Earth fault loop impedance (Zs) | Reg. 411.3 |
| Acceptable voltage at the load | Voltage drop calculation | Reg. 525 |
Key point: A cable size that passes the current-carrying check can still fail on voltage drop, and a protective device that’s right for overload may not be fast enough for fault disconnection. You have to check all the criteria, not just the obvious one.
Overload vs Fault Current — Know the Difference
The regulations treat these as two separate problems:
| Overload Current | Fault Current | |
|---|---|---|
| Cause | Excess load on a healthy circuit | Insulation failure (L-L, L-N, L-E) |
| Magnitude | Modest — typically 1.1 to 5 × In | Very high — hundreds to thousands of amps |
| Onset | Gradual | Instantaneous |
| Governed by | Regulation 433 | Regulation 434 |
| Device part used | Thermal element / inverse-time curve | Magnetic element / instantaneous trip |
A 32 A Type B MCB on a B6 curve will tolerate 3 to 5 × In before instantaneous trip — that’s 96 to 160 A. Below that, it relies on the thermal element to clear an overload over seconds or minutes.
The Overload Coordination Rule: Ib ≤ In ≤ Iz
This is the single most important inequality in Part 4. Regulation 433.1 states:
Ib ≤ In ≤ Iz
| Symbol | Meaning |
|---|---|
| Ib | Design current of the circuit — the current the circuit is intended to carry |
| In | Rated (nominal) current of the protective device |
| Iz | Current-carrying capacity of the cable, after correction factors |
Read in plain English: the cable must be able to carry the design current, and the protective device must be small enough that it trips before the cable is overloaded.
Exam tip: A common wrong answer pairs a 32 A MCB with a cable whose Iz, after derating, is only 27 A. Even though the cable’s tabulated capacity is 32 A or more, the corrected Iz is what counts. Always derate first.
The I2 ≤ 1.45 × Iz Check
The second condition in Regulation 433.1 is:
I2 ≤ 1.45 × Iz
Where I2 is the operating current of the device — the current at which it’s guaranteed to disconnect within conventional time.
| Device Type | I2 Value | Automatic? |
|---|---|---|
| BS EN 60898 MCB | 1.45 × In | Yes — automatically satisfied if Ib ≤ In ≤ Iz |
| BS EN 61009 RCBO | 1.45 × In | Yes |
| BS 88 HRC fuse | 1.6 × In | Yes — well within 1.45 × Iz when derated |
| BS 3036 rewireable fuse | 2 × In | No — apply a 0.725 factor to Iz |
Remember: For modern devices (MCBs, RCBOs, HRC fuses) the I2 check is automatic — you only need to verify Ib ≤ In ≤ Iz. The exam likes to test the BS 3036 edge case because that’s the one where the 0.725 correction factor must be applied.
Applying Correction Factors to Iz
The tabulated current-carrying capacity in Appendix 4 (typically called It) is the capacity under reference conditions: 30 °C ambient, one circuit, no grouping, no thermal insulation. Real-world installations rarely meet those conditions, so we derate:
Iz = It × Ca × Cg × Ci × Cc × Cs
| Factor | What It Corrects For | Where Found |
|---|---|---|
| Ca | Ambient temperature ≠ 30 °C | Table 4B1 |
| Cg | Grouping of circuits | Table 4C1 |
| Ci | Thermal insulation surrounding the cable | Reg. 523.9 |
| Cc | Buried cables / BS 3036 fuses | Note in 433.1.101 |
| Cs | Soil thermal resistivity (buried only) | Table 4B3 |
The procedure is also covered in detail in our cable size calculation guide — work through a couple of full examples and the steps stick.
Important: When multiple factors apply, multiply them all together. A 2.5 mm² T&E with It of 27 A, in an ambient of 40 °C (Ca = 0.87), grouped with two other circuits (Cg = 0.7), gives Iz = 27 × 0.87 × 0.7 = 16.4 A. That’s only suitable for a 16 A device — not the 20 A you might assume from the table.
Voltage Drop — Regulation 525
A cable that’s thermally adequate can still produce unacceptable voltage drop on a long run. Regulation 525 sets the limits:
| Circuit | Max Voltage Drop | 230 V Equivalent |
|---|---|---|
| Lighting | 3% | 6.9 V |
| All other circuits | 5% | 11.5 V |
The calculation uses the mV/A/m values from Appendix 4:
Vd = (mV/A/m × Ib × L) ÷ 1000
For a 25 m run of 2.5 mm² T&E (mV/A/m = 18) carrying 20 A:
Vd = (18 × 20 × 25) ÷ 1000 = 9.0 V
That’s 3.9% on 230 V — fine for a power circuit, fail for a lighting circuit.
Exam tip: Voltage drop is the calculation most candidates forget to check after they’ve sized the cable. Look out for long-run scenarios — submains, garden offices, outbuildings, EV chargers — where the volt-drop check, not the thermal check, drives the cable size up. See our EV charger cable calculation guide for a fully worked example.
Fault Protection and Disconnection Times
Overcurrent protection handles overload; fault protection ensures the device disconnects fast enough to prevent dangerous touch voltages persisting under earth fault conditions.
Maximum Disconnection Times (Reg. 411.3.2)
| System | Final Circuits ≤ 32 A | Distribution / > 32 A |
|---|---|---|
| TN | 0.4 s | 5 s |
| TT | 0.2 s | 1 s |
To meet these times automatically using overcurrent protection alone, Zs × Ia ≤ U0 must hold — i.e. the earth fault loop impedance must be low enough that fault current exceeds the device’s instantaneous trip threshold (Ia) at U0 = 230 V.
Table 41.3 gives the maximum permitted Zs values for each device type and rating. The full open-book technique for using this table — including the 80% rule for live measurements — is covered in Maximum Zs and the 80% Rule.
The CPC and the Adiabatic Equation
A circuit’s protective conductor (CPC) must be large enough to carry fault current for the disconnection time without exceeding its insulation’s permitted temperature rise. Two options:
| Method | Reference |
|---|---|
| Table 54.7 — minimum CPC based on line conductor size | Quick, conservative |
| Adiabatic equation — S = √(I²t) / k | Reg. 543.1.3 — minimum CPC for the actual fault scenario |
| Line Conductor | Minimum CPC (Table 54.7) |
|---|---|
| Up to 16 mm² | Same size as line |
| Over 16 up to 35 mm² | 16 mm² |
| Over 35 mm² | Half the line conductor |
For tight cases — typically twin-and-earth where the CPC is smaller than the line conductor — use the adiabatic to confirm adequacy. The adiabatic equation explained post walks through the maths step by step.
When Overload Protection Can Be Omitted
Regulation 433.3 permits omission of overload protection in specific situations:
| Scenario | Example |
|---|---|
| Cable not capable of overload | Fixed-load resistive heater on its own dedicated circuit |
| Omission would not cause danger | Safety circuits where disconnection is worse than overload |
| Cable already protected upstream | Tap-off from a main where the upstream device gives overload protection |
Important: Even when overload protection is omitted, fault protection is still required. The two are governed by different regulations and addressed by different parts of the device’s characteristic.
Worked Example: A 32 A Radial Circuit
A 32 A radial socket circuit, 28 m long, in 2.5 mm² T&E clipped direct, ambient 30 °C, no grouping, no insulation.
| Step | Check | Result |
|---|---|---|
| 1 | Ib = design current | 32 A (assumed full load) |
| 2 | In = device rating | 32 A Type B MCB |
| 3 | It = Appendix 4 capacity (Method C, 2.5 mm²) | 27 A |
| 4 | Iz after correction (Ca = Cg = Ci = 1) | 27 A |
| 5 | Check Ib ≤ In ≤ Iz: 32 ≤ 32 ≤ 27 | FAIL |
2.5 mm² is not adequate at the full load — Iz is 27 A but In is 32 A. The circuit needs 4 mm² (It = 37 A, Iz = 37 A, passes). For a typical domestic radial, designers usually accept that Ib will be well below 32 A in practice, but the strict Regulation 433 check uses In, not Ib.
The ring final circuit is the classic workaround — two paths in parallel raise Iz, allowing 2.5 mm² to be protected by 32 A. The catch, of course, is that breaking the ring at one point removes a current path. See overload in a ring final circuit for the full analysis.
Common Exam Traps
| Trap | Why It Catches People Out |
|---|---|
| Skipping the I2 check for BS 3036 fuses | Rewireable fuses have I2 = 2 × In — the 0.725 factor on Iz is mandatory |
| Comparing In to It instead of Iz | The corrected capacity is what matters — apply Ca, Cg, Ci first |
| Forgetting voltage drop on long runs | The thermal check passes but the 3%/5% limit fails |
| Mixing up disconnection times | TT systems need 0.2 s for final circuits, not 0.4 s |
| Using Table 54.7 without checking adiabatic | Table 54.7 is conservative — sometimes a smaller CPC is permitted, sometimes Table 54.7 itself isn’t enough |
| Reading 1.45 × Iz as “the cable’s safe maximum” | It isn’t — Iz is the safe maximum. 1.45 × Iz is the operating threshold for the device, not a thermal limit for the cable |
Practice and Further Study
Circuit design questions appear right across Parts 4, 5, and 6 of the exam, and the calculations build on each other. The best preparation is repetition — work the same sums in different forms until the procedure is automatic.
- Part 4 — Protection for Safety quiz — overload, fault, RCD requirements
- Part 5 — Selection and Erection of Equipment quiz — cable sizing, voltage drop, CPCs
- Part 6 — Inspection and Testing quiz — verifying your design against measured values
Our app includes 580+ practice questions with worked explanations referencing specific BS 7671 regulations, plus full timed mock exams that mirror the real 60-question paper. Calculation questions are flagged so you can drill them in isolation when revising.
Study on the go with our mobile app: App Store | Google Play