Part 4Cable SizingCalculationsDesign

How to Calculate Cable Size and Protective Device Rating: The BS 7671 Procedure

IET Wiring Regulations Team ·

Cable sizing is the calculation that electricians and designers get asked about most often — and it’s the question that appears in almost every IET exam. Get it wrong, and you end up with a cable that either overheats (too small) or costs far more than necessary (too big).

 

This guide walks you through the full BS 7671 cable sizing procedure, from design current to final verification, with a worked example you can follow along with.

 

 

The Key Rule: Ib ≤ In ≤ It

Before diving into the steps, you need to understand the fundamental relationship that governs cable sizing in BS 7671:

 

The key relationship: Ib ≤ In ≤ It

 

SymbolMeaning
Ib (design current)The actual current the circuit needs to carry
In (nominal rating)The rating of the protective device (MCB, fuse, RCBO)
It (tabulated current)The current-carrying capacity of the cable

 

Fundamental Rule: The device rating (In) must be at least as big as the design current (Ib), and the cable (It) must be able to carry at least as much as the device rating (In). This ensures the cable is always protected against overload: Ib ≤ In ≤ It.

 

The Cable Sizing Procedure — Step by Step

Cable sizing procedure flowchart

 

Step 1: Determine the Design Current (Ib)

The design current is the maximum current the circuit will normally carry. How you calculate it depends on the type of load:

 

Load TypeFormula / Method
Resistive loads (heaters, kettles)Ib = P ÷ V (e.g., 3000W ÷ 230V = 13.0A)
Motor loadsUse the motor’s full-load current from the manufacturer’s data
Diversity (multiple loads)Apply diversity factors per BS 7671 Appendix 1

 

Step 2: Select the Protective Device (In)

Choose an MCB, fuse, or RCBO with a rating equal to or greater than Ib. Standard MCB ratings are: 6, 10, 16, 20, 25, 32, 40, 50, 63A.

 

For example, if Ib = 28A, the next standard MCB rating up is 32A, so In = 32A.

 

Note: You must also consider the type of MCB (B, C, or D) based on the load characteristics. Type B is standard for most domestic circuits. Type C is used for motor loads with higher inrush currents, and Type D for very high inrush loads such as transformers.

 

Step 3: Apply Correction Factors

This is where most exam candidates struggle. The cable’s published current rating (from BS 7671 tables) assumes ideal installation conditions: 30°C ambient temperature, cables not grouped together, no thermal insulation, and an MCB or HRC fuse as the protective device.

 

If conditions differ from the ideal, you need correction factors that increase the required cable capacity.

 

Correction factors explained

 

The four main correction factors are:

FactorWhat it accounts forTypical valuesBS 7671 Reference
CaAmbient temperature above 30°C0.94 (35°C) to 0.50 (70°C)Table 4B1
CgGrouping (cables bunched together)0.65 to 1.00Tables 4C1–4C4
CiThermal insulation contact0.50 (surrounded) to 1.00Reg. 523.7
CfBS 3036 fuse (rewirable)0.725Reg. 433.1.1

 

The required tabulated current capacity of the cable is:

It = In ÷ (Ca × Cg × Ci × Cf)

 

If no correction factor applies, use 1.0 for that factor.

 

Step 4: Select the Cable from Tables

Look up the appropriate BS 7671 current-carrying capacity table for your installation method (e.g., Table 4D5 for thermoplastic flat cable clipped direct). Find a cable size where the tabulated current (It) is greater than or equal to your calculated minimum It.

 

Step 5: Check Voltage Drop

Even if the cable can carry the current safely, it may drop too much voltage over a long run. BS 7671 limits the voltage drop to:

Circuit TypeMaximum Voltage DropAs Voltage
Lighting circuits3% of 230V6.9V
Other circuits5% of 230V11.5V

Key Limit: If the voltage drop exceeds these limits, you must increase the cable size — a bigger cable has lower resistance per metre and therefore less voltage drop.

 

Voltage drop check

 

The formula is:

VD = (mV/A/m × Ib × L) ÷ 1000

 

Where:

  • mV/A/m = millivolts per amp per metre (from BS 7671 Table 4D5)
  • Ib = design current in amps
  • L = cable length in metres (one way, not total)

 

Step 6: Check Earth Fault Loop Impedance (Zs)

Finally, verify that the earth fault loop impedance for the circuit is low enough to ensure the protective device will trip within the required disconnection time. This check is covered in detail in our separate guide on testing Zs.

 

Worked Example

Scenario: A 9.2 kW electric shower is to be installed in a bathroom. The cable run is 18 metres, clipped direct to a wall, at 30°C ambient. The cable passes through 200mm of loft insulation. The circuit is protected by a Type B MCB.

 

Step 1 — Design current:

Ib = P ÷ V = 9200 ÷ 230 = 40A

 

Step 2 — Protective device:

Next standard MCB rating ≥ 40A = 40A Type B MCB

 

Step 3 — Correction factors:

FactorValueReason
Ca1.030°C ambient — no correction needed
Cg1.0Single circuit — no grouping
Ci0.75Cable passes through insulation but not surrounded (Reg. 523.7)
Cf1.0MCB, not a BS 3036 fuse

 

Minimum It = 40 ÷ (1.0 × 1.0 × 0.75 × 1.0) = 53.3A

 

Step 4 — Cable selection:

From Table 4D5 (Method C — clipped direct), a 10 mm² T&E cable has a tabulated current of 64A, which is ≥ 53.3A. ✓

 

Step 5 — Voltage drop:

From Table 4D5, the mV/A/m for 10 mm² is 4.4.

VD = (4.4 × 40 × 18) ÷ 1000 = 3.17V

3.17V is well within the 5% limit of 11.5V. ✓

 

Result: Use 10 mm² T&E cable with a 40A Type B MCB. The cable’s 64A rating exceeds the 53.3A minimum required after correction factors, and the 3.17V voltage drop is well within the 11.5V limit.

 

Common Mistakes

MistakeProblemSolution
Forgetting to apply correction factorsCable undersized — risk of overheatingAlways check Ca, Cg, Ci, and Cf
Using the wrong installation method tableIncorrect current ratings selectedMatch the table to your actual installation method
Calculating voltage drop with total cable lengthVD appears twice as high as actualUse one-way cable length, not there-and-back
Selecting In less than IbProtective device trips under normal loadIn must be ≥ Ib — always round up to next standard rating
Ignoring thermal insulationCable in loft insulation overheatsApply Ci = 0.50 (surrounded) or 0.75 (touching one surface)

 

Key Regulations

RegulationRequirement
Reg. 433.1Overload protection: Ib ≤ In ≤ Iz
Reg. 433.1.1BS 3036 fuse factor (0.725)
Reg. 523.7Cables in thermal insulation
Appendix 4Current-carrying capacity and voltage drop tables
Table 4B1Ambient temperature correction factors
Tables 4C1–4C4Grouping correction factors
Table 4D5Current ratings for flat T&E cable
Appendix 12Voltage drop limits

 

Practice and Further Study

Cable sizing calculations are covered under Part 4: Protection for Safety and Part 5: Selection and Erection of Equipment of BS 7671. Test your knowledge:

 

Study on the go with our mobile app: App Store | Google Play

Prepare for your exam with our mobile app

580+ practice questions with detailed explanations