Extending Radial Circuits: Sockets, Spurs, Lighting and Cable Sizes Explained

IET Wiring Regulations Team ·
Extending Radial Circuits: Sockets, Spurs, Lighting and Cable Sizes Explained

“Can I add another socket?” is one of the most common questions electricians get asked, and one of the most common they ask each other. The answer is almost always “yes, but…”. The “but” is usually about cable size, protective device rating, and where on the circuit you connect.

 

Radial circuits are everywhere in domestic work: immersion heaters, cookers, lighting, and more and more socket circuits. Extending them correctly means applying the core design principles of Part 4 and Part 5 of BS 7671 to real installations. That’s exactly the kind of practical understanding the 18th Edition exam is built to test.

 

This guide covers what a radial circuit is, the design rule every extension must meet, the rules for extending 16A, 20A and 32A socket radials, how to spur lighting from a socket circuit, and the 3 metre rule that allows smaller cables in some cases.

What Is a Radial Circuit?

A radial circuit leaves the consumer unit, runs out to its points of use, and stops. Unlike a ring final circuit, it never returns to its starting point.

 

A radial circuit can serve:

 

TypeExamplesPoints of Use
Dedicated radialImmersion heater, cooker, shower, EV chargerOne
Multi-point radialLighting circuits, radial socket circuitsSeveral

 

An immersion heater circuit is the classic dedicated radial. It runs from its own circuit breaker or fuse in the consumer unit directly to the heater. A lighting circuit is also a radial: it feeds one ceiling rose after another, and the circuit ends at the last point.

 

Key point: The defining feature of a radial is that it does not return to the consumer unit. That’s why it’s tested differently from a ring. There’s no end-to-end ring continuity test, and R1+R2 is measured at the furthest point. See our ring vs radial testing comparison for the full method.

 

The Design Rule Every Extension Must Satisfy

Before you add anything to a circuit, it must still meet the overload coordination requirement of Regulation 433.1.1:

 

Ib ≤ In ≤ Iz

 

SymbolMeaningIn Plain Terms
IbDesign currentWhat the load actually draws
InNominal rating of the protective device (OCPD)The breaker or fuse rating, which must be at least Ib
IzCurrent-carrying capacity of the cable under its installation conditionsThe cable rating, which must be at least In and never smaller

 

Work in order: find the design current, choose a device rated at least that high, then choose a cable whose current-carrying capacity (after rating factors) is equal to or greater than the device rating.

 

Remember: Iz is not a fixed number for a given cable size. It depends on the installation reference method and on rating factors for ambient temperature, grouping and thermal insulation. If the cable runs through a loft, an insulated wall or trunking, its capacity drops, even though the load stays the same. Our guide to installation reference methods and cable sizing explains how to read Appendix 4 correctly.

 

Typical Radial Circuits and Their Ratings

The figures below assume reference method C (clipped direct) for twin and earth cable, the simplest installation condition. They’re examples to show the principle, not a complete design table.

 

CircuitIb (Design Current)In (Device)CableApprox. Iz (Method C)
Immersion heater (3 kW)13A16A2.5 mm²27A
Immersion flex from 13A FCU13A13A fuse1.5 mm² flex~20A
Cooker (approx. 7 kW)~30A (before diversity)32A6 mm²47A
Lighting2–3A (LED)6A MCB / 5A fuse1.0 or 1.5 mm²16A / 20A
Sockets (radial)Varies16A or 20A2.5 mm²27A
Sockets (radial)Varies32A4 mm²37A

 

Each line satisfies Ib ≤ In ≤ Iz. For the immersion heater, 13A ≤ 16A ≤ 27A. At the fused connection unit, 13A ≤ 13A ≤ 20A. Both are fine.

 

A few practical notes:

  • An immersion heater should be on its own dedicated circuit.
  • A cooker needs a dedicated circuit and a cooker control switch, which may include a 13A socket outlet.
  • Some electricians use 1.5 mm² for the lighting loop and 1.0 mm² for switch drops, which makes the loop cables easy to tell apart from the switch cables at the ceiling rose.

 

Exam tip: Questions often give you Ib and a reference method and ask for the minimum device rating or cable size. Always check the cable’s tabulated rating after applying rating factors. That’s where most wrong answers come from. For worked examples, see Circuit Design and Overload Protection.

 

Extending 16A and 20A Socket Radials

This is the simplest case. If the circuit is protected by a 16A or 20A circuit breaker (or a 15A/20A fuse) and is wired entirely in 2.5 mm² twin and earth, the cable (27A, method C) is always rated above the protective device.

 

Overload protection is therefore assured wherever you connect, so there’s no restriction on:

 

ArrangementPermitted?
Sockets anywhere along the circuit✅ Yes
Spurs from sockets✅ Yes
Spurs from spurs✅ Yes
Junction boxes feeding sockets✅ Yes
Any mix of single, double or treble outlets✅ Yes

 

What you do need to check is circuit length, because the extra cable increases voltage drop and earth fault loop impedance. The maximum Zs at the furthest point must still meet the Table 41.3 limit for the device (or 80% of it when measured cold).

 

Important: A double socket outlet should not be loaded above 20A in total. It has two 13A outlets, but plugging in two 13A room heaters (26A) is bad practice. Design for the worst case you can reasonably expect.

 

Extending 32A Socket Radials

With a 32A device, cable size matters, because 2.5 mm² cable (27A) is now rated below the device. The main run, the radial trunk, must be in 4 mm² twin and earth (37A, method C).

 

Here are the rules for connecting to a 32A radial:

 

ConnectionCable to the SpurWhat’s Allowed
Socket on the trunk4 mm²Single or double socket anywhere on the trunk
Spur(s) in 4 mm²4 mm²Any number of single or double sockets, all joined in 4 mm²
Spur in 2.5 mm² from a socket2.5 mm²One single or one double socket only
Spur in 2.5 mm² from a junction box2.5 mm²One single or one double socket only. The circuit must stop there
13A FCU on the trunk1.5 mm² or largerAny reasonable number of sockets, protected by the 13A fuse

 

Why the 2.5 mm² Spur Is Limited to One Outlet

A 2.5 mm² spur isn’t protected against overload by the 32A breaker. It’s acceptable only because its load is naturally limited: one double socket shouldn’t exceed 20A, which is within the cable’s 27A rating.

 

If you add a second socket, two 13A heaters could draw 26A or more and push the cable towards its limit. That’s why two single sockets do not count as one double. Each separate outlet adds another potential 13A load.

 

The FCU Option

A 13A fused connection unit connected to the 4 mm² trunk changes everything downstream. The 13A fuse now provides overload protection, so the outgoing cable can drop to 1.5 mm² (about 20A, method C) and supply several sockets. Fault protection and Zs must still be checked for the whole downstream circuit.

 

Key point: On a 32A radial, the cable size at every point must suit the device that protects it. On the 4 mm² trunk, that’s the 32A breaker. After a 13A FCU, it’s the 13A fuse. A single-outlet 2.5 mm² spur is the only exception, because its load is limited by design.

 

Spurring Lighting from a Socket Circuit

Sometimes the only practical way to light a new space, such as a conservatory built off a dining room, is to take a supply from the socket circuit. It’s allowed, but you must reduce the protection to suit the lighting cable. Normally you’d take only one lighting spur.

 

MethodSupply Into FCUFCUOut of FCU
From a socket on the trunk2.5 mm²3A FCU1.5 mm² to switch and lamp
From a junction box2.5 mm²3A FCU1.5 mm² to ceiling rose (three-plate method)
Switched FCU on the trunk4 mm² trunk3A switched FCU (acts as the light switch)1.5 mm² to the lamp

 

These rules apply whether the socket circuit is on a 16A, 20A or 32A device.

 

Remember: Use a 3A fuse, not 13A, in a lighting FCU. A 13A fuse wouldn’t protect 1.0 mm² or 1.5 mm² lighting cable or lampholders properly.

 

Notice the cable sizes in the socket and junction box examples: 4 mm² on the trunk, 2.5 mm² to the FCU, and 1.5 mm² after it. At every point the cable suits the protection upstream of it, except where the next regulation gives you some leeway.

 

The 3 Metre Rule

Regulation 433.2.2 lets you place the overload protective device along the run of a conductor, away from the point where the cable size is reduced, provided the section between the reduction and the device:

 

ConditionRequirement
LengthNot more than 3 m
BranchesNo branch circuits
OutletsNo socket outlets or other outlets of any kind
InstallationInstalled to reduce the risk of fault to a minimum and to reduce the risk of fire or danger to persons

 

In practice, this means the cable from a socket or junction box to a 3A FCU can be 1.5 mm² instead of 2.5 mm², as long as it’s a single unbranched run of no more than 3 m.

 

Exam tip: Questions on Regulation 433.2.2 often hinge on the details: 3 m maximum, no branches, no outlets. A distractor might offer 2 m or 5 m, or describe a cable with a socket part-way along. Tab Section 433 in your book.

 

Before You Extend: The Checks That Matter

Extending any circuit is a design decision, not just a wiring job. Before you add a point, work through these checks:

 

CheckWhat to ConfirmWhere in BS 7671
OverloadIb ≤ In ≤ Iz at every pointReg. 433.1.1
Installation conditionsRating factors for thermal insulation, grouping, ambient temperatureAppendix 4
Voltage dropWithin 3% (lighting) / 5% (other uses) for public suppliesReg. 525 / Appendix 4
Earth fault loop impedanceZs at the furthest point within the Table 41.3 limitReg. 411.4.4 / Table 41.3
Additional protection30 mA RCD for sockets ≤ 32A and cables concealed in wallsReg. 411.3.3 / Reg. 522.6.202
Floor area servedWithin Appendix 15 guidance (e.g. 50 m² for a 20A radial, 75 m² for a 32A radial)Appendix 15
Existing installationExisting circuit is safe and suitable for the additionReg. 132.16

 

Important: Regulation 132.16 says no addition or alteration may be made to an existing installation unless the rating and condition of the existing equipment are adequate for the altered circumstances, and the earthing and bonding are adequate. Extending a circuit that’s already faulty or overloaded isn’t compliant, however neat your new work is.

 

Quick Summary

  • A radial circuit goes from the supply to its points of use and stops.
  • A 16A or 20A radial wired entirely in 2.5 mm² can be extended without spur restrictions, subject to Zs and voltage drop.
  • A 32A radial needs a 4 mm² trunk. Any number of spurs is fine if they’re also in 4 mm².
  • A 2.5 mm² spur from a 32A trunk supplies one single or one double socket only.
  • A 13A FCU on the trunk allows 1.5 mm² downstream cable to several sockets.
  • Lighting spurs use a 3A FCU (or a 3A switched FCU) and 1.5 mm² cable.
  • Regulation 433.2.2 allows a reduced cable size for up to 3 m, with no branches and no outlets.

 

Practice and Further Study

Radial circuit design brings together overload protection (Part 4), cable selection (Part 5) and verification (Part 6). That’s exactly the kind of cross-part question the 18th Edition exam likes to ask. Test yourself:

 

Our app includes 690+ practice questions covering all 8 parts of BS 7671. Each one has a detailed explanation that references the specific regulation number. You also get topic-specific quizzes to target weak areas such as overload protection and cable sizing, and timed mock exams that use the same weighted question distribution as the real City & Guilds 2382-26 exam.

 