Trunking and Conduit Calculations: How to Use Appendix E of the On-Site Guide
“How many cables can I pull through this conduit?” and “How full should the trunking be?” are two of the most common questions asked by apprentices and by experienced electricians who should probably know better. The honest answer is that there is no single guaranteed figure, but there is a simple, repeatable method.
That method lives in Appendix E of the IET On-Site Guide. It turns every cable and every size of conduit or trunking into a number called a factor. Add up the cable factors, compare the total with the containment factor, and you have your answer.
This guide walks through the method and four worked examples, covering short straight conduit runs, long runs with bends, and trunking.
In This Guide
- Why Containment Capacity Matters
- The Method: Cable Factors vs Containment Factors
- Which Appendix E Table Do I Use?
- Worked Example 1: Will These Cables Fit?
- Worked Example 2: Choosing a Conduit Size
- Worked Example 3: Long Runs and Bends
- Worked Example 4: Trunking
- Common Mistakes to Avoid
- Practice and Further Study
Why Containment Capacity Matters
The main reason for limiting the number of cables is ease of drawing in. Overfill a conduit and you risk stretching conductors and stripping insulation as the cables are pulled through, and that damage is hidden inside the containment where nobody will see it.
BS 7671 sets the underlying requirement. Regulation 522.8.1 requires a wiring system to be selected and erected so that damage to cables during installation, use and maintenance is avoided. Appendix E of the On-Site Guide is the practical tool for meeting it.
Several things affect how many cables will really fit:
| Factor | Why It Matters |
|---|---|
| Cable damage during drawing in | The first consideration, because tight pulls damage insulation |
| Cable size variations | Insulation thickness varies between manufacturers and between solid and stranded conductors |
| Containment tolerances | Internal dimensions vary, and plastic trunking usually has thicker walls than metal |
| Loading and grouping | More loaded conductors in one enclosure means more heat and lower current-carrying capacity |
| Mixed cable types | Thermoplastic (PVC) and thermosetting cables in the same containment need care |
Important: Appendix E only tells you whether the cables will physically fit without damage. It does not tell you whether they can carry their load. Grouping must be dealt with separately using the rating factors in Appendix 4 of BS 7671. See our guide to rating factors and cable sizes.
One more point of good practice: Appendix E is written for single-core insulated cables. Twin and earth does not belong in conduit, so install singles.
The Method: Cable Factors vs Containment Factors
Every calculation in Appendix E follows the same three steps:
- Find the cable factor for each conductor and add them all together
- Find the conduit or trunking factor for the containment (for conduit, this depends on diameter, length and number of bends)
- Compare the two: the containment factor must be equal to or greater than the total cable factor
Key point: Sum of cable factors ≤ conduit or trunking factor. If that statement is true, the quantity of cables is acceptable.
The method answers two different questions, and you simply run it in a different direction for each:
| Question | Start With | Then |
|---|---|---|
| Will these cables fit in this conduit or trunking? | The containment factor for the installed size | Check the total cable factor does not exceed it |
| What size conduit or trunking do I need? | The total cable factor | Select the first containment size with a factor equal to or greater than the total |
Which Appendix E Table Do I Use?
There are six tables arranged as three pairs. Choosing the right pair is half the battle.
| Situation | Cable Factors | Containment Factors |
|---|---|---|
| Conduit: straight runs of 3 m or less | Table E1 | Table E2 |
| Conduit: straight runs over 3 m, or any length with bends | Table E3 | Table E4 |
| Trunking | Table E5 | Table E6 |
Remember: Never mix the pairs. A 6 mm² cable has a factor of 88 in Table E1 but 58 in Table E3. The numbers only mean something when compared with the matching containment table.
Table and page numbers quoted here are from the On-Site Guide used in the worked examples. Check them against your own copy, as page numbers shift between editions. If you are new to the guide, our walkthrough of the On-Site Guide’s standard final circuit tables is a good companion to this post.
Worked Example 1: Will These Cables Fit?
An existing 20 mm conduit runs straight for 2.5 m. You need to draw in the following single-core cables:
| Cables | Quantity | Table E1 Factor | Total |
|---|---|---|---|
| 2.5 mm² solid (two line and neutral pairs) | 4 | 39 | 156 |
| 2.5 mm² stranded (two line and neutral pairs) | 4 | 43 | 172 |
| 1.5 mm² stranded (two line and neutral pairs) | 4 | 31 | 124 |
| Total cable factor | 452 |
It is a straight run under 3 m, so Table E2 gives the conduit factor: 460 for 20 mm conduit.
452 ≤ 460, so the conduit is acceptable, but only just.
Exam tip: Stranded conductors have a higher cable factor than solid conductors of the same cross-sectional area. The small air gaps between strands make the overall cable slightly larger. Read the question carefully to see which type is specified.
Worked Example 2: Choosing a Conduit Size
This time the cables are known and the conduit is not. Select a straight conduit, 3 m long, for these stranded singles:
| Cables | Quantity | Table E1 Factor | Total |
|---|---|---|---|
| 1.5 mm² (2 line, 2 neutral, 2 CPC) | 6 | 31 | 186 |
| 2.5 mm² (2 line, 2 neutral, 2 CPC) | 6 | 43 | 258 |
| 6 mm² (1 line, 1 neutral, 1 CPC) | 3 | 88 | 264 |
| Total cable factor | 708 |
Here each CPC is the same size as its line conductor, in line with Regulation 543.1.4 and Table 54.7 of BS 7671. If you want to justify a smaller CPC by calculation, that is a job for the adiabatic equation.
Now look down Table E2 for the first conduit factor equal to or greater than 708:
| Conduit Diameter | Table E2 Factor | Suitable? |
|---|---|---|
| 20 mm | 460 | No |
| 25 mm | 800 | Yes |
Select 25 mm conduit.
Worked Example 3: Long Runs and Bends
Table E4 looks daunting at first glance, but it breaks down into simple parts:
| Part of Table E4 | What It Tells You |
|---|---|
| Left-hand column | Length of the conduit run in metres |
| Blank area, top left | Straight runs of 3 m or less, where you use Tables E1 and E2 instead |
| Straight block | Conduit factors for straight runs over 3 m, by diameter |
| Four bend blocks | Conduit factors for runs with one, two, three or four bends |
| Bottom of table | Multipliers for larger conduit sizes |
Now the example. An 8 m conduit run with two bends is to carry three 6 mm² singles: one line, one neutral and one CPC.
Step 1: Cable factor. The run has bends, so use Table E3. A 6 mm² cable has a factor of 58.
3 × 58 = 174
Step 2: Conduit factor. In Table E4, find the 8 m row and follow it across to the block for two bends. You need a factor of at least 174. The first value that achieves this is 292. Follow that column up to the top of the table and it reads 25 mm.
Select 25 mm conduit.
Key point: Every bend and every extra metre reduces the conduit factor. A conduit that comfortably takes a set of cables on a short straight run may be too small for the same cables over a longer run with bends.
Worked Example 4: Trunking
Trunking uses Tables E5 and E6, and there is no length or bend element because cables are laid in rather than drawn in. The trunking factors are built around a space factor of roughly 45%. As a rule of thumb, cables should fill no more than about half of the internal space.
A 75 mm × 25 mm metal trunking already contains 12 circuits, each with three 2.5 mm² PVC stranded singles. You are asked to add two more circuits, each with three 4 mm² PVC stranded singles. Will it still comply?
| Cables | Quantity | Table E5 Factor | Total |
|---|---|---|---|
| 2.5 mm² PVC stranded (existing) | 36 | 12.6 | 453.6 |
| 4 mm² PVC stranded (additional) | 6 | 16.6 | 99.6 |
| Total cable factor | 553.2 |
Table E6 gives a trunking factor of 738 for 75 mm × 25 mm trunking.
553.2 ≤ 738, so the additional circuits can be installed and the trunking still complies with Appendix E.
Important: The data is based on metal trunking. Plastic trunking usually has thicker walls, so there is less space inside for the same nominal size. Reduce the trunking factor or increase the cable factors slightly to allow for this. Plastic also holds heat in, where metal conducts it away.
Fitting is only half the answer here. With 14 circuits in one trunking, grouping factors will have a serious effect on current-carrying capacity. Our guide to installation reference methods and Appendix 4 covers that side of the design.
Common Mistakes to Avoid
| Mistake | Why It Goes Wrong |
|---|---|
| Using Table E1 factors with Table E4 | The pairs are not interchangeable, so the answer will be wrong |
| Forgetting the CPCs | Every conductor in the conduit counts, not just lines and neutrals |
| Ignoring solid vs stranded | The factors are different for the same cross-sectional area |
| Counting circuits instead of cables | Multiply the factor by the number of individual conductors |
| Rounding down to a smaller conduit | The containment factor must be equal to or greater than the total, with no exceptions |
| Treating “it fits” as “it complies” | Grouping and loading still have to be checked against BS 7671 |
Remember: Appendix E is a guide, not a guarantee. Use common sense as well. If the numbers only just work and the run is awkward, go up a size.
Practice and Further Study
Containment calculations become quick with practice. Pick a few cable combinations, work through the tables in both directions, and check that you chose the correct pair of tables each time.
Appendix E supports the selection and erection requirements of Part 5 of BS 7671, so that is the best place to test your wider knowledge:
The 18th Edition Prep app gives you practice questions across all 8 parts of BS 7671 with detailed explanations referencing specific regulation numbers. It has topic-specific quizzes so you can focus on weak areas such as Part 5 wiring systems, and timed mock exams that mirror the weighting and time pressure of the real thing.