BS 7671Regulations

IP Codes in the 18th Edition Exam: How to Find Them and 8 Worked Questions

IET Wiring Regulations Team ·
IP Codes in the 18th Edition Exam: How to Find Them and 8 Worked Questions

IP codes come up in almost every 18th Edition exam paper. Most candidates know roughly what “IP44” means. The trouble is that BS 7671 doesn’t always use IP codes. Some regulations give the requirement as an IP number, others use the book’s own AD and AE external influence codes, and some use both.

 

If you can’t move between the two systems, or you can’t find the right page quickly, you’ll spend minutes on a question that should take seconds. This guide covers how IP codes work, where they sit in BS 7671, and the pattern that makes special location questions easy. It finishes with eight exam-style questions worked through step by step.

How an IP Code Is Built

IP stands for Ingress Protection. The code is defined in BS EN 60529 and tells you how well an enclosure keeps out solid objects and water. It is made of two digits, sometimes followed by an extra letter.

 

PositionProtects AgainstRange
First digitSolid foreign objects (fingers, tools, wire, dust)0–6
Second digitWater (drips, sprays, splashes, jets, immersion)0–8
Additional letter (optional)Access to hazardous partsA–D

 

First Digit — Solids

DigitProtection Against
2Objects ≥ 12.5 mm (a finger)
3Objects ≥ 2.5 mm (a tool or thick wire)
4Objects ≥ 1.0 mm (a thin wire)
5Dust-protected
6Dust-tight

 

Second Digit — Water

DigitProtection Against
2Dripping water when tilted up to 15°
3Spraying water
4Splashing water from any direction
5Water jets
6Powerful water jets
7Temporary immersion
8Continuous submersion

 

Additional Letters — Access to Hazardous Parts

LetterAccess Prevented For
ABack of the hand
BFinger
CTool (2.5 mm)
DWire (1.0 mm)

 

Remember: Solids first, water second, every time. In IP44 the first 4 is for solid objects and the second 4 is for water.

 

Why the X Matters

The letter X holds a place. It means “not specified” for that position, and you can’t drop it.

 

CodeSolidsWaterMeaning
IPX4Not specified4Splash protection only
IP4X4Not specifiedProtection against objects ≥ 1 mm only
IP4444Both, a common requirement for outdoor and agricultural equipment
IPXXBNot specifiedNot specifiedFinger cannot reach hazardous parts
IPXXDNot specifiedNot specified1 mm wire cannot reach hazardous parts

 

If a question just said “IP4”, you couldn’t tell whether it meant IPX4 or IP4X. Those are two quite different requirements. Exam questions use this to build plausible wrong answers, so read every character of each option.

 

Exam tip: IPXXB and IP2X are written side by side in Regulation 416.2.1, and IPXXD and IP4X in 416.2.2. Learn them as pairs, because an answer option will often give just one of the two forms.

 

Appendix 5: AD and AE Codes

BS 7671 has its own way of classifying external influences, set out in Appendix 5 — Classification of External Influences. Each influence gets a two-letter code and a number. Only two of the categories have IP equivalents:

 

CategoryInfluenceIP Equivalent?
ADPresence of waterYes, second digit
AEPresence of solid foreign bodiesYes, first digit
AA, AB, AC, etc.Temperature, humidity, altitude and othersNo

 

Appendix 5 starts with a summary table of the codes and then gives a fuller description of each one. The detailed pages are where the IP equivalents appear. On the summary page, “AD4 — splashes” doesn’t tell you much. The detailed entry explains the type and direction of the splash and gives the IP equivalent.

 

AD — Water

CodeDescriptionApproximate IP Equivalent
AD1NegligibleIPX0
AD2Free-falling dropsIPX1 / IPX2
AD3SpraysIPX3
AD4SplashesIPX4
AD5JetsIPX5
AD6WavesIPX6
AD7ImmersionIPX7
AD8SubmersionIPX8

 

AE — Solid Foreign Bodies

CodeDescriptionApproximate IP Equivalent
AE1NegligibleIP0X
AE2Small objects (2.5 mm)IP3X
AE3Very small objects (1 mm)IP4X
AE4Light dustIP5X
AE5Moderate dustIP5X / IP6X
AE6Heavy dustIP6X

 

Important: Don’t assume the AD number always matches the IP number. AD4 = IPX4 and AD5 = IPX5, but that doesn’t hold for every code. The AE numbers are offset as well: AE3 is IP4X, not IP3X. Always check the table.

 

So IP44 corresponds to AD4 + AE3. That’s the combination you’ll see in several Part 7 sections. For a broader look at using the appendices under exam conditions, see our guide to learning the appendices for the 18th Edition exam.

 

Where IP Codes Appear in BS 7671

IP requirements are spread across the book. These are the places worth tabbing:

 

LocationReferenceWhat You’ll Find
Appendix 5Classification of External InfluencesAD/AE codes and IP equivalents
Section 416Regs 416.2.1 and 416.2.2Basic protection by barriers or enclosures
Section 701Reg 701.512.2Bathroom zone IP ratings
Section 702Reg 702.512.2Swimming pool zone IP ratings
Section 705Reg 705.512.2Agricultural and horticultural premises
Section 708Reg 708.512.2Caravan and camping parks
Index”IP codes” and “Degrees of protection”Cross-references to every location with a requirement

 

The index is worth more than people expect. If you look up “IP codes”, it sends you to the degree of protection entry, which lists most of the regulations that set an IP requirement. Our guide to using the contents page and index explains how to use both under time pressure.

 

Keep the numbering logic in mind too. A regulation in the 400s is a general Part 4 requirement. A regulation in the 700s is a special location and supplements the general rules.

 

Key point: The On-Site Guide has a short appendix summarising IP codes, only a couple of pages long, and it’s very useful when a question names the OSG directly. Don’t overlook it.

 

The 512.2 Pattern for Special Locations

This is the most useful shortcut in the guide. In Part 7, the external influences requirement for each special location sits under the same number: the section number followed by .512.2.

 

Special LocationSectionExternal Influences RegulationKey IP Requirement
Bathrooms701701.512.2Zone 0: IPX7. Zones 1 and 2: IPX4 (IPX5 where water jets are used for cleaning)
Swimming pools702702.512.2Zone 0: IPX8 (AD8). Zone 1: IPX4 (IPX5 where jets are used)
Agricultural/horticultural705705.512.2At least IP44
Caravan/camping parks708708.512.2AD4 and AE3, i.e. IP44

 

Why IPX7 in a bath but IPX8 in a pool? Depth. A pool is much deeper than a bathtub, and deeper water means greater pressure on the enclosure, so continuous submersion protection is needed. Notice that the pool regulation gives both forms, IPX8 and AD8. BS 7671 sometimes uses IP codes, sometimes AD/AE codes and sometimes both, and you need to be comfortable with all three.

 

Exam tip: When a question names a special location and asks for a degree of protection, go straight to [section].512.2. You don’t need to read the whole section.

 

For a fuller look at bathroom and pool zones, see Special Locations in BS 7671: Bathrooms, Swimming Pools, and More.

 

8 Worked Exam Questions

Try each question before you read the answer. Each one says where to look, which is how you build the navigation habit you’ll need on exam day.

 

Question 1

Section 416 of BS 7671 requires that the horizontal top surface of a barrier or enclosure which is readily accessible shall provide a degree of protection of at least:

a) IPXXB or IP2X b) IPX4 c) IPXXD or IP4X d) IP44

 

Answer: c. Regulation 416.2.2 requires at least IPXXD or IP4X for readily accessible horizontal top surfaces. The stricter rating is there because small objects such as wire can be dropped onto a top surface.

 

Question 2

According to the On-Site Guide, a degree of protection of IPXXB indicates that:

a) Access with the back of a hand shall not be possible b) Access with a 1 mm wire shall not be possible c) The enclosure is protected against splashing water d) Access with a finger shall not be possible

 

Answer: d. The additional letter B means a finger can’t reach hazardous parts. Look it up in the IP code appendix of the On-Site Guide.

 

Question 3

Section 416 requires that live parts shall be inside enclosures or behind barriers providing a degree of protection of at least:

a) IPXXD or IP4X b) IPX7 c) IP44 d) IPXXB or IP2X

 

Answer: d. Regulation 416.2.1 gives IPXXB or IP2X. Don’t mix it up with Question 1: the general requirement is finger-proof, and the top surface requirement is wire-proof.

 

Question 4

In a room containing a bath or shower, installed electrical equipment in Zone 0 shall have a degree of protection of at least:

a) IPX4 b) IPX5 c) IPX8 d) IPX7

 

Answer: d. Go to Section 701 and then Regulation 701.512.2. Zone 0 requires at least IPX7.

 

Question 5

In a swimming pool location, installed electrical equipment in Zone 0 shall have a degree of protection of at least:

a) IPX7 b) IPX8 c) IPX5 d) IP44

 

Answer: b. Section 702, Regulation 702.512.2, requires IPX8 (AD8) in Zone 0. Use the same .512.2 pattern as in Question 4.

 

Question 6

In agricultural and horticultural premises, electrical equipment should have a degree of protection of at least:

a) IP44 b) IPX4 c) IP2X d) IPX8

 

Answer: a. Section 705, Regulation 705.512.2, requires at least IP44. Livestock, dust and wash-downs mean both digits need a rating, so IPX4 alone isn’t enough.

 

Question 7

With reference to Appendix 5 of BS 7671, splashes of water would be classified as external influence category:

a) AD4 b) AD3 c) AE4 d) AD5

 

Answer: a. AD4 is splashes. AD3 is sprays and AD5 is jets. AE4 is a solids code, so it can’t be right for a water question.

 

Question 8

With reference to Appendix 5 of BS 7671, an external influence of AE3 is considered equivalent to:

a) IP3X b) IP4X c) IPX3 d) IPX4

 

Answer: b. AE3 covers very small objects of 1 mm, which is IP4X. This question is aimed squarely at people who assume the numbers line up. AE is a solids code, so the digit goes in the first position, and it’s a 4, not a 3.

 

Key point: Four of these eight questions name the exact section or appendix to use. The real exam often does the same, so the marks go to whoever can turn to the right page fastest.

 

Common Mistakes with IP Codes

MistakeHow to Avoid It
Swapping the digitsSolids first, water second, every time
Ignoring the XIPX4 and IP4X are different requirements
Assuming AE3 = IP3XAE codes are offset. AE3 = IP4X
Mixing up 416.2.1 and 416.2.2General enclosure = IPXXB/IP2X. Top surface = IPXXD/IP4X
Using IPX7 for a poolPools are deeper, so Zone 0 is IPX8
Reading an entire Part 7 sectionGo straight to [section].512.2
Forgetting the On-Site GuideWhen the OSG is named, its IP appendix is the quickest route

 

IP ratings matter beyond the exam as well. During inspection you’ll be expected to spot equipment without an adequate degree of protection for where it’s installed. Our PIR sensor and outside light wiring guide shows how this works on a typical external installation.

 

Practice and Further Study

IP code questions draw on Part 4, Part 7 and the Appendices. Test yourself on the relevant topics:

 

Our app includes 690+ practice questions covering all 8 parts. Each one has a detailed explanation that cites the regulation number, so you learn where the answer sits in the book as well as what it is. Use the topic-specific quizzes to drill Part 7 and Appendix 5. Then sit timed mock exams that use the same weighted question distribution as the real City & Guilds 2382-26 paper.

 

Study on the go with our mobile app: App Store | Google Play

Prepare for your exam with our mobile app

690+ practice questions with detailed explanations