Part 6: Inspection and Testing - What You Need to Know
Overview of Part 6
Part 6 of BS 7671 deals with the inspection and testing of electrical installations. Although it has fewer questions (28 in our question bank), it’s critically important for both the exam and real-world practice.
Exam weight: Part 6 accounts for approximately 4 out of 60 questions (7% of the exam). Despite the lower question count, the testing sequence and insulation resistance values are among the most frequently examined topics in the entire paper.
In This Guide
Key Concepts
Initial Verification (Chapter 61)
Before an installation is put into service, it must undergo initial verification comprising:
- Visual inspection: Checking for compliance without instruments
- Testing: Using appropriate test instruments to verify safety
Inspection Requirements (Section 611)
Visual inspection should confirm:
| Requirement | What to Check |
|---|---|
| Connection of conductors | All conductors correctly terminated and secure |
| Conductor sizing | Adequate for the circuit’s design current |
| Fire barriers and seals | Present and intact where required |
| Labelling and identification | All circuits and devices properly marked |
| Accessibility | Equipment accessible for maintenance |
Testing Sequence (Section 612)
Tests must be carried out in a specific order:
| Step | Test | Purpose |
|---|---|---|
| 1 | Continuity of protective conductors | Confirms CPCs are intact (dead test) |
| 2 | Continuity of ring final circuit conductors | Confirms ring is not broken (dead test) |
| 3 | Insulation resistance | Verifies insulation integrity — 500V DC, min 1.0 MΩ (dead test) |
| 4 | Polarity | Confirms L and N are correctly connected (dead test) |
| 5 | Earth fault loop impedance | Compares Zs against Table 41.3 values (live test) |
| 6 | RCD operation | Verifies trip time and current (live test) |
Key principle: Dead tests always come before live tests. You don’t energise the circuit until you’ve confirmed it’s sound.
Periodic Inspection (Chapter 62)
Existing installations require periodic inspection to determine:
- Safety for continued use
- Any deterioration or damage
- Changes that may have occurred since last inspection
Common Exam Questions
Part 6 questions often focus on:
| Topic | What to Know |
|---|---|
| Correct sequence of tests | Dead tests first, then live tests — order matters because each test depends on the previous result |
| Minimum insulation resistance values | 500V DC test voltage with a minimum reading of 1.0 MΩ |
| When periodic inspection is required | Determined by installation type, environment, and previous condition |
| Documentation requirements | New work = EIC, minor additions = MEIWC, periodic inspection = EICR |
Practice Part 6 Questions
Test your knowledge with our Part 6 practice quiz containing 28 focused questions on inspection and testing procedures.