CalculationsBS 7671

Fuse Size Not Listed? How to Calculate Maximum Zs from Appendix 3

IET Wiring Regulations Team ·
Fuse Size Not Listed? How to Calculate Maximum Zs from Appendix 3

Table 41.2 of BS 7671 gives maximum earth fault loop impedance (Zs) values for fuses that must disconnect within 0.4 seconds. The trouble is that it doesn’t list every fuse. Look up a BS 88-3 or BS 3036 fuse above a certain rating and the table simply stops.

 

Electricians often ask what to do when the fuse they’ve fitted isn’t in the table. You don’t need a different book or a manufacturer’s datasheet. BS 7671 already gives you what you need in Appendix 3, and one short formula turns that data into a maximum Zs value.

 

This guide covers where to find the data, how to use the formula, how to round the answer, and how to turn a tabulated value into one you can check against your test readings. All references are to BS 7671:2018+A4:2026.

Why Some Fuse Sizes Are Missing

The maximum Zs tables in Chapter 41 are there to make life easier. They cover the ratings you meet most often on final circuits. They don’t try to cover every rating made, and for several fuse types the 0.4 s data stops at 63 A.

 

TableWhat It CoversDisconnection Time
Table 41.2Fuses: BS 88-2, BS 88-3, BS 3036, BS 13620.4 s
Table 41.3Circuit-breakers: Types B, C and D0.4 s and 5 s
Table 41.4Fuses for distribution circuits and the 5 s condition5 s

 

Larger fuses obviously exist. You’ll find 80 A and 100 A BS 88-3 cut-outs, and 100 A BS 3036 rewireables in older installations. If you need to confirm one of these will disconnect in 0.4 s, the tables won’t give you the answer directly.

 

Key point: The tabulated Zs values were calculated from the fuse time/current characteristics in the first place. Those characteristics are printed in Appendix 3, so you can do the same calculation for any rating shown there.

 

If you’re not sure which Chapter 41 table applies to your device, read our guide on Zs tables and which one to use first.

 

Where the Data Lives: Appendix 3

Appendix 3 contains the time/current characteristic curves for every protective device type BS 7671 covers. People also call them response curves or tripping curves. Each device type has its own figure, and some types run across two figures so the graphs stay readable. BS 3036 fuses are an example.

 

The curves themselves are hard to read accurately. In the corner of each figure, though, is a small data table. It lists, for each fuse rating, the fault current needed to disconnect the fuse within set times such as 0.1 s, 0.2 s, 0.4 s and 5 s.

 

What You’re ReadingWhat It Means
Figure headingThe device type (e.g. BS 88-3 system C). Check it before you read anything else
ColumnRequired disconnection time (0.4 s, 5 s, etc.)
RowFuse rating in amperes
Value where they crossIa, the fault current (in amperes) the fuse needs to disconnect within that time

 

Important: The values in the Appendix 3 data table are currents, not impedances. You have to put them through the formula below before you can compare them with anything in Chapter 41.

 

The Maximum Zs Formula

Appendix 3 also gives the equation that links fault current to loop impedance. It’s just Ohm’s law with a voltage correction:

 

Zs = (U0 × Cmin) ÷ Ia

 

SymbolMeaningValue
ZsMaximum earth fault loop impedanceWhat we’re solving for (Ω)
U0Nominal AC line voltage to earth230 V (most UK installations)
CminMinimum voltage factor, allowing for supply voltage variation0.95
IaCurrent causing disconnection within the required timeFrom Appendix 3 (A)

 

The top line of the formula is always the same for a standard 230 V installation:

 

230 × 0.95 = 218.5 V

 

So in practice the formula becomes Zs = 218.5 ÷ Ia. Only the bottom number changes from one calculation to the next.

 

Exam tip: Check the formula against a value you already know. Pick a rating that is listed in Table 41.2, read its Ia from Appendix 3 and run the calculation. Your answer should match the table. If it does, you’re reading the right figure and the right column. If rearranging formulae makes you nervous, our guide to transposition of electrical formulae covers the maths.

 

Worked Examples

The Ia values below are the ones used in this worked method. In the exam and on site, always read Ia from the figure in your own copy of BS 7671. Don’t rely on numbers you remember or got from someone else.

 

Example 1: 80 A BS 88-3 System C Fuse, 0.4 s

Table 41.2 stops at 63 A for this fuse type, so go to the BS 88-3 system C figure in Appendix 3.

 

  1. Confirm the figure heading reads BS 88-3 system C
  2. Find the 0.4 s column
  3. Follow it down to the 80 A row
  4. Read the required fault current: Ia = 750 A

 

StepWorking
FormulaZs = (U0 × Cmin) ÷ Ia
SubstituteZs = (230 × 0.95) ÷ 750
Calculate218.5 ÷ 750 = 0.29133
AnswerZs = 0.29 Ω

 

Example 2: 100 A BS 88-3 System C Fuse, 0.4 s

Use the same figure. Find the 0.4 s column and the 100 A row: Ia = 1050 A.

 

StepWorking
SubstituteZs = 218.5 ÷ 1050
Calculate0.20809
AnswerZs = 0.21 Ω

 

Example 3: 100 A BS 3036 Fuse, 0.4 s

BS 3036 semi-enclosed (rewireable) fuses have very different characteristics from BS 88 fuses, so expect a different answer at the same rating. Their Appendix 3 data is split across two figures. Make sure you use the one that covers 100 A.

 

From the data table: 0.4 s column, 100 A row, Ia = 1200 A.

 

StepWorking
SubstituteZs = 218.5 ÷ 1200
Calculate0.18208
AnswerZs = 0.18 Ω

 

Remember: At the same 100 A rating, the BS 3036 fuse needs more fault current than the BS 88-3 fuse to clear in 0.4 s. More fault current means a lower maximum Zs. Any fuse that is slower to operate needs a lower-impedance fault path to make up for it.

 

Rounding Up or Down

People argue about this a lot. The approach here follows standard mathematical rounding to two decimal places, which is the normal precision for Zs and R1+R2 values.

 

Look only at the third decimal place:

 

Third Decimal DigitActionExampleResult
0–4Leave the second decimal as it is0.291330.29
5–9Add one to the second decimal0.208090.21
5–9, rolls overThe carry can change more than one digit0.2990.30
5–9, rolls overIt can carry right through to the whole number1.999882.00

 

Some textbooks always round up and some always round down. Whichever you use, the difference is a few thousandths of an ohm. In practice your measured readings will usually be well below the maximum, so it won’t decide a pass or fail.

 

Key point: If you want to be cautious, remember that a Zs value is a maximum. Rounding a maximum down gives a slightly stricter limit and never a more lenient one. In an exam, choose the option that matches correct mathematical rounding of your calculated figure.

 

From Tabulated Zs to Measured Zs

The values you’ve just calculated are tabulated values, like those in Table 41.2. They assume conductors at their maximum operating temperature. Your loop impedance tester measures the circuit cold, so you can’t compare a test reading with them directly.

 

To get a limit you can use on site, multiply the tabulated value by 0.8:

 

FuseTabulated Zs× 0.8Maximum Measured Zs
80 A BS 88-3 system C0.29 Ω× 0.80.23 Ω
100 A BS 88-3 system C0.21 Ω× 0.80.17 Ω
100 A BS 30360.18 Ω× 0.80.14 Ω

 

Warning: A measured reading of 0.25 Ω on the 80 A BS 88-3 circuit looks fine against 0.29 Ω. It fails against the 0.23 Ω limit. Once the cable is at full load temperature, the impedance would rise above the value needed for 0.4 s disconnection.

 

Our guide on maximum Zs and the 80% rule explains why the factor is 0.8 and how it relates to the 1.2 multiplier for calculated R1+R2. For the test procedure itself, see testing Zs earth fault loop impedance.

 

Practise It Yourself

Doing the calculations yourself is what makes the method stick. Find the time/current figures for BS 88-2 fuses (systems E and G) in Appendix 3. Choose five ratings that aren’t listed in Table 41.2 and work out the tabulated 0.4 s Zs for each.

 

RatingIa from Appendix 3 (0.4 s)218.5 ÷ IaTabulated Zs (2 d.p.)× 0.8 Measured Zs
Rating 1
Rating 2
Rating 3
Rating 4
Rating 5

 

Then check your method: run one listed BS 88-2 rating through the same steps and make sure your answer matches Table 41.2.

 

Exam tip: Do the same for the 5 s column and compare your answers with Table 41.4. Exam questions on distribution circuits use the 5 s condition, and the method is exactly the same apart from the column you read.

 

The Method in Five Steps

StepAction
1Find the time/current figure for your exact device type in Appendix 3 and check the heading
2Read Ia where the required disconnection-time column meets your fuse rating row
3Calculate Zs = (230 × 0.95) ÷ Ia, which is the same as 218.5 ÷ Ia
4Round to two decimal places. This is your tabulated maximum Zs
5Multiply by 0.8 to get the maximum Zs you can accept from a test meter reading

 

Once you’ve done this a few times, a missing fuse rating stops being a problem. The same method works for any device in Appendix 3, so an unlisted rating takes you a couple of minutes.

 

Practice and Further Study

Zs calculations come up regularly in the 18th Edition exam, and quick navigation between Chapter 41 and Appendix 3 saves you time. Test yourself with these:

 

Our app has 690+ practice questions covering all 8 Parts and the Appendices. Each answer comes with an explanation that cites the regulation number. You’ll also find topic-specific quizzes for drilling Chapter 41 and Appendix 3 calculations, and timed mock exams with the same weighted question distribution as the real City & Guilds 2382-26 paper.

 

Study on the go with our mobile app: App Store | Google Play

Prepare for your exam with our mobile app

690+ practice questions with detailed explanations