2391 Inspection and Testing Questions and Answers: 8 Worked Examples
Inspection and testing questions are where many candidates lose easy marks. That’s true on the City & Guilds 2391 and on the Part 6 section of the 18th Edition exam. The calculations aren’t difficult. The marks go because candidates misread what the question is asking, forget a step, or use the wrong book.
Below are eight worked questions of the kind you’ll meet in inspection and testing exams. For each one we give the answer, show where to find it in BS 7671, Guidance Note 3 or the On-Site Guide, and explain why that answer is right in practice.
To get the most out of this, cover the answer and try each question yourself before reading on.
In This Guide
- The Questions at a Glance
- Question 1: Extending a Lighting Circuit
- Question 2: Putting Tests in the Correct Order
- Question 3: Preparing for a Prospective Fault Current Test
- Question 4: Maximum Earth Electrode Resistance on a TT System
- Question 5: Recording Ipf on the Schedule of Test Results
- Question 6: Measuring Ze Accurately
- Question 7: Calculating Zs for a Radial Circuit
- Question 8: R1+R2 for a Ring Final Circuit
- Quick-Reference Summary
- Practice and Further Study
The Questions at a Glance
| No. | Topic | Where to Find It |
|---|---|---|
| 1 | R1+R2 after extending a circuit | GN3 Table B1 / OSG Table I1 |
| 2 | Order of tests | Reg. 643 / OSG testing checklist |
| 3 | Ipf test preparation | GN3 / OSG test procedures |
| 4 | TT earth electrode resistance | Reg. 411.5.3 / Table 41.5 |
| 5 | Recording Ipf | GN3 / schedule of test results |
| 6 | Measuring Ze | GN3 / OSG test procedures |
| 7 | Zs calculation | Zs = Ze + (R1+R2) |
| 8 | Ring final R1+R2 | (r1 + r2) ÷ 4 |
Important: Page numbers change between editions of BS 7671 and the guidance notes, so learn the regulation and table numbers rather than page numbers. Make sure your books match the version your exam is based on.
Question 1: Extending a Lighting Circuit
A new lighting point is added in a domestic hallway. It’s wired from the existing ceiling rose to a new ceiling rose so that both lights work from the same switch. The new cable is 1.5/1.0 mm² twin and earth, 7 m long. Before the new cable was connected, R1+R2 at the original ceiling rose measured 1.30 Ω.
What R1+R2 reading would you expect at the new ceiling rose?
| Option | Value |
|---|---|
| A | 0.21 Ω |
| B | 1.51 Ω |
| C | 1.30 Ω |
| D | 2.11 Ω |
Answer: B — 1.51 Ω
Look up the 1.5/1.0 mm² copper combination in Guidance Note 3 Table B1 or On-Site Guide Table I1. The combined R1+R2 resistance is 30.20 mΩ per metre at 20°C.
| Step | Calculation | Result |
|---|---|---|
| New cable resistance | 30.20 mΩ/m × 7 m | 211.4 mΩ |
| Convert to ohms | 211.4 ÷ 1,000 | 0.21 Ω |
| New total R1+R2 | 1.30 + 0.21 | 1.51 Ω |
Exam tip: Option A is the trap. It’s the resistance of the new cable only. The question asks for the reading at the new ceiling rose, which includes the whole circuit back to the distribution board. Always add the new section to the existing value.
For more on the test itself, see our guide to continuity of protective conductors and the R1+R2 test.
Question 2: Putting Tests in the Correct Order
Four tests are listed:
- Polarity
- Earth fault loop impedance
- Continuity of protective conductors
- Insulation resistance
What is the correct order for carrying out these tests?
| Option | Order |
|---|---|
| A | 1, 3, 4, 2 |
| B | 4, 3, 1, 2 |
| C | 3, 1, 4, 2 |
| D | 3, 4, 1, 2 |
Answer: D — 3, 4, 1, 2
The order comes from Regulation 643 (initial verification) in BS 7671. The On-Site Guide’s testing checklist follows the same order. Some tests in the full sequence are missing from this list, but that doesn’t matter. Just put these four in their relative order.
| BS 7671 Order | Test | Regulation |
|---|---|---|
| 1st | Continuity of protective conductors | Reg. 643.2 |
| 2nd | Insulation resistance | Reg. 643.3 |
| 3rd | Polarity | Reg. 643.6 |
| 4th | Earth fault loop impedance | Reg. 643.7.3 |
Warning: Guidance Note 3 describes the tests in an order that doesn’t exactly match the regulation sequence. That section explains how to do each test. It isn’t the approved testing order. For questions about order, use BS 7671 or the On-Site Guide checklist.
The reason for the order is safety. Dead tests confirm the circuit is sound before you energise it for live tests such as Zs.
Question 3: Preparing for a Prospective Fault Current Test
You’re testing a domestic TN-S installation and need to measure prospective fault current (Ipf) at the consumer unit.
What must you do before making the test?
| Option | Statement |
|---|---|
| A | Leave the main switch on and disconnect the main earthing conductor from the MET |
| B | Switch off the main switch and disconnect the main earthing conductor from the MET |
| C | Leave the main switch on with all circuits loaded |
| D | Switch off the main switch, carry out safe isolation checks, and leave the main earthing conductor connected to the MET |
Answer: D
With the earthing conductor connected, the measurement includes every parallel path to earth, such as main bonding to gas and water pipes. Parallel paths lower the impedance, which raises the fault current. That gives you the maximum current that could flow during a fault, and that’s the figure you need to check that protective devices can handle it.
The test is made on the supply side of the main switch, between the incoming line and the earth terminal. Some instruments use three leads (line, neutral, earth) and some only need two (line and earth).
Remember: Even with the main switch off, the incoming terminals are live. This is a live test. Use GS38-compliant leads and take suitable precautions. Learn how your own test meter works before assessment day.
Question 4: Maximum Earth Electrode Resistance on a TT System
A TT installation is protected by a 300 mA RCD. You measure earth fault loop impedance to the earth electrode with a loop tester.
What is the maximum acceptable reading?
| Option | Value |
|---|---|
| A | 1,667 Ω |
| B | 500 Ω |
| C | 200 Ω |
| D | 167 Ω |
Answer: D — 167 Ω
You can find this two ways.
From the table: Look up 300 mA in Table 41.5 of BS 7671 and read off 167 Ω.
From the formula: Regulation 411.5.3 requires RA × IΔn ≤ 50 V. Rearrange it with Ohm’s law:
RA = 50 V ÷ 0.3 A = 166.7 Ω ≈ 167 Ω
The 50 V is the touch voltage limit: the highest voltage that may appear on exposed-conductive-parts before the RCD disconnects.
| RCD Rating (IΔn) | Maximum RA (50 V ÷ IΔn) |
|---|---|
| 30 mA | 1,667 Ω |
| 100 mA | 500 Ω |
| 300 mA | 167 Ω |
| 500 mA | 100 Ω |
Key point: Guidance Note 3 notes that an electrode resistance above 200 Ω may not be stable, because soil drying or freezing can change it. That’s why option C is there as a distractor. For this question, the regulation limit is the answer.
Our TT earthing system guide covers electrodes and RCD selection in more detail.
Question 5: Recording Ipf on the Schedule of Test Results
First, be clear about the two measurements:
| Measurement | Tested Between | What It Tells You |
|---|---|---|
| PEFC (prospective earth fault current) | Line and earth | Current flowing during a line–earth fault |
| PSCC (prospective short-circuit current) | Line and neutral | Current flowing during a line–neutral short circuit |
Results are usually shown in kiloamps. For example, 0.63 kA = 630 A.
During a periodic inspection of a single-phase TN-S domestic installation, you get PEFC = 0.63 kA and PSCC = 0.71 kA.
What should you record for Ipf?
| Option | Value |
|---|---|
| A | 0.63 kA |
| B | 0.71 kA |
| C | 1.34 kA |
| D | 1.42 kA |
Answer: B — 0.71 kA
Record the higher of the two readings, because that’s the worst case. This is a single-phase installation, so record the value as measured. Don’t add the readings together (option C), and don’t double them (option D).
Exam tip: The doubling rule only applies to three-phase supplies. There, line-to-line PSCC is commonly approximated as twice the single-phase line-to-neutral value. Check whether the question says single-phase or three-phase before you answer.
Question 6: Measuring Ze Accurately
To prove the main earthing conductor is effective and get an accurate Ze value, what must you do?
| Option | Statement |
|---|---|
| A | Isolate the installation and disconnect the main earthing conductor from the MET |
| B | Leave the installation energised and the earthing conductor connected |
| C | Isolate the installation and leave the earthing conductor connected |
| D | Disconnect all main protective bonding conductors only |
Answer: A
This is the opposite of Question 3, and it’s set up to catch you out. Disconnecting the earthing conductor from the MET removes parallel paths through bonding and extraneous-conductive-parts. Those paths could give a falsely low reading. They could also hide an earthing conductor that isn’t actually connected to anything at the supply end.
| Test | Earthing Conductor | Why |
|---|---|---|
| Ipf | Left connected | Want the highest current (lowest impedance) |
| Ze | Disconnected from MET | Want the highest impedance (true external path only) |
If the worst-case Ze passes, the installation will only be better once you reconnect the earthing conductor. On a TT system, disconnect only at the MET and leave the electrode connection in place.
Important: The installation is isolated, but this is still a live test at the origin. Always reconnect the main earthing conductor before you re-energise.
Question 7: Calculating Zs for a Radial Circuit
A radial final circuit is protected by a 16 A Type B circuit-breaker to BS EN 60898. Test results: Ze = 0.32 Ω and R1+R2 = 0.72 Ω.
What should you record as the maximum measured Zs?
| Option | Value |
|---|---|
| A | 0.40 Ω |
| B | 0.72 Ω |
| C | 0.23 Ω |
| D | 1.04 Ω |
Answer: D — 1.04 Ω
Zs = Ze + (R1+R2) = 0.32 + 0.72 = 1.04 Ω
As a check, the Table 41.3 maximum for a 16 A Type B device is 2.73 Ω. Apply the 80% rule and the limit is about 2.18 Ω, so 1.04 Ω passes comfortably. Our guide to Maximum Zs and the 80% Rule explains why that correction matters.
Question 8: R1+R2 for a Ring Final Circuit
After the end-to-end continuity tests on a ring final circuit, you get r1 = 0.50 Ω (line conductors) and r2 = 0.83 Ω (protective conductors).
What should you record for R1+R2?
| Option | Value |
|---|---|
| A | 1.33 Ω |
| B | 0.67 Ω |
| C | 0.33 Ω |
| D | 0.21 Ω |
Answer: C — 0.33 Ω
R1+R2 = (r1 + r2) ÷ 4 = (0.50 + 0.83) ÷ 4 = 0.33 Ω
Some books write the formula as “(L–L + E–E) ÷ 4”, which means the same thing. You divide by four because cross-connecting the ring halves the length of each path, and the two paths then run in parallel, which halves the resistance again.
Remember: For 2.5/1.5 mm² twin and earth, r2 should be about 1.67 × r1. Here, 0.50 × 1.67 = 0.835, so these readings are consistent. That makes a useful sanity check in the exam and on site.
Quick-Reference Summary
| Concept | Formula / Rule |
|---|---|
| Extended circuit R1+R2 | Original R1+R2 + (mΩ/m × length ÷ 1,000) |
| Test order | Continuity → insulation resistance → polarity → Zs (Reg. 643) |
| Ipf test | Earthing conductor connected |
| Ze test | Earthing conductor disconnected from MET |
| TT electrode limit | RA = 50 V ÷ IΔn (Table 41.5) |
| Recording Ipf | Higher of PEFC and PSCC |
| Zs | Ze + (R1+R2) |
| Ring R1+R2 | (r1 + r2) ÷ 4 |
Practice and Further Study
Inspection and testing questions reward practice. The more worked examples you go through, the faster you’ll spot the traps. Test yourself with our Part 6 — Inspection and Testing quiz and the Part 4 — Protection for Safety quiz.
The 18th Edition Prep app includes hundreds of practice questions across all 8 parts of BS 7671, with explanations that cite specific regulation numbers. It also has topic-specific quizzes so you can focus on weak areas like Part 6, and timed mock exams that match the real exam’s question weighting.
Study on the go with our mobile app: App Store | Google Play